
7–77
62-11785
07008
CHECK REDUNDANT RETURN AIR SENSOR (RAT2)
• ACTIVATION: A Redundant Return Air Temperature Sensor (RAT2) is installed, configure, and is not within
the range of -53 to +158°F (-47 to +70° C).
• UNIT CONTROL: If RAT2 is selected as the active probe, switch active probe to RAT probe.
• RESET CONDITION: Auto reset when sensor is in range or, alarm may be manually reset using the
display mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
1.
Check Sensor
a. Inspect sensor & connectors. Verify there is no damage to sensor, and no damage, moisture, or
corrosion in connectors.
b. Check sensor resistance. (Refer to Note 3 in
Section) 10,000 Ohms @ 77°F (25°C). Refer to
for chart of resistances for different sensors.
2.
Check Sensor Wiring
a. Inspect connector pins & terminals at sensor connector 2MM. (See wiring schematic
Verify there is no physical damage to harness, and no damage, moisture, or corrosion in connectors.
b. Place the system in PC Mode. Refer to Note 2 in
Section Disconnect sensor from harness.
Check for 3.0 ± 0.1 VDC at harness plug between pins. Voltage should be 3.0 ± 0.1 VDC volts at
harness plug between pins. This verifies microprocessor.
07009
RETURN AIR SENSORS OUT OF RANGE (RAT & RAT2)
• ACTIVATION: A Redundant Return Air Temperature Sensor (RAT2) is installed, configure, and is not
reading with (2° C).
• UNIT CONTROL: If RAT2 is selected as the active probe, switch active probe to RAT probe.
• RESET CONDITION: Auto reset when sensor is in range or, alarm may be manually reset using the
display mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
1.
Check Sensor
a. Inspect sensor & connectors. Verify there is no damage to sensor, and no damage, moisture, or
corrosion in connectors.
b. Check sensor resistance. (Refer to Note 3 in
Section) 10,000 Ohms @ 77°F (25°C). Refer to
for chart of resistances for different sensors.
2.
Check Sensor Wiring
a. Inspect connector pins & terminals at sensor connector 2MM. (See wiring schematic
Verify there is no physical damage to harness, and no damage, moisture, or corrosion in connectors.
b. Place the system in PC Mode. Refer to Note 2 in
Section Disconnect sensor from harness.
Check for 3.0 ± 0.1 VDC at harness plug between pins. Voltage should be 3.0 ± 0.1 VDC volts at
harness plug between pins. This verifies microprocessor.
Summary of Contents for VECTOR 8100
Page 2: ......
Page 4: ......
Page 12: ...62 11785 viii ...
Page 16: ...62 11640 12 ...
Page 18: ...62 11785 ...
Page 24: ...62 11785 1 6 1 3 SAFETY DECALS ...
Page 25: ...1 7 62 11785 ...
Page 26: ...62 11785 1 8 ...
Page 27: ...1 9 62 11785 ...
Page 28: ...62 11785 1 10 ...
Page 30: ...62 11785 ...
Page 50: ...62 11785 ...
Page 82: ...62 11785 ...
Page 96: ...62 11785 4 14 ...
Page 98: ...62 11785 ...
Page 129: ...5 31 62 11785 ...
Page 130: ...62 11785 5 32 ...
Page 134: ...62 11785 6 4 ...
Page 138: ...62 11785 ...
Page 230: ...62 11785 ...
Page 271: ...8 41 62 11785 ...
Page 272: ...62 11785 8 42 ...
Page 274: ...62 11785 ...
Page 286: ......
Page 287: ......
Page 288: ...62 11785 10 8 ...
Page 292: ......
Page 293: ......