
7–9
62-11785
00022
LOW SUCTION SUPERHEAT
• ACTIVATION: Alarms
00127 CHECK SUCTION TEMP SENSOR
and/or
are not active and Compressor suction superheat (Compressor Suction Temperature (CST)
minus saturated temperature for Compressor Suction Pressure (CSP) is less than 8°F (4.4°C) for more
than 3-4 minutes.
• UNIT CONTROL: Refrigeration system shutdown and alarm with PSCON still energized.
• RESET CONDITION: Auto reset after 15 minutes, or alarm may be manually reset using the display
mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see
if any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check System
Pressures
a. Check Suction and Evaporator Pressure reading at the compressor. While the compressor is
running and the SMV is greater than 70% open, verify evaporator and suction pressure read within
3 psig of each other, with evaporator pressure slightly higher than suction pressure. If not, check
transducers. Refer to
b. Install manifold gauge set and check and compare compressor discharge, suction and evaporator
outlet pressure to the Unit Data readings. Refer to
for instruction on comparison.
2.
Check Evaporator
Section
- Check evaporator section, return air bulkhead, air chute, and the evapora-
tor coil (for cleanliness and airflow). Refer to
.
3.
Check Suction and Evaporator Temperature
Sensors
a. Check Evaporator and Suction temperature sensor insulation integrity, and make sure insulation is
properly installed. Repair or replace any insulation if required. Loose or missing insulation will
cause inaccurate refrigerant temperature readings.
b. Inspect sensor & connector. Verify there is no damage to sensor. Verify there is no damage,
moisture, or corrosion in connector.
c. Check sensor resistance (Refer to Note 3 in
Section). 10,000 Ohms @ 77°F (25°C.) See
for complete table of temperatures and resistance values.
4.
Check Expansion Valve
(EVXV)
a. Visually inspect valve. Check that the coil is seated properly.
b. Check operation of valve. Refer to
.
5.
Perform Pretrip
Check
- Clear Active Alarm list, then run Pretrip & check for any new alarms. Any active
alarms must be corrected and cleared before proceeding.
Summary of Contents for VECTOR 8100
Page 2: ......
Page 4: ......
Page 12: ...62 11785 viii ...
Page 16: ...62 11640 12 ...
Page 18: ...62 11785 ...
Page 24: ...62 11785 1 6 1 3 SAFETY DECALS ...
Page 25: ...1 7 62 11785 ...
Page 26: ...62 11785 1 8 ...
Page 27: ...1 9 62 11785 ...
Page 28: ...62 11785 1 10 ...
Page 30: ...62 11785 ...
Page 50: ...62 11785 ...
Page 82: ...62 11785 ...
Page 96: ...62 11785 4 14 ...
Page 98: ...62 11785 ...
Page 129: ...5 31 62 11785 ...
Page 130: ...62 11785 5 32 ...
Page 134: ...62 11785 6 4 ...
Page 138: ...62 11785 ...
Page 230: ...62 11785 ...
Page 271: ...8 41 62 11785 ...
Page 272: ...62 11785 8 42 ...
Page 274: ...62 11785 ...
Page 286: ......
Page 287: ......
Page 288: ...62 11785 10 8 ...
Page 292: ......
Page 293: ......