WIRING CHECK function
Introduction
The WIRING CHECK function allows to check and correct the connections.
For it to work properly, the following three conditions must be met:
1. the set system must be “3P+N”,
2. all voltages must be connected,
3. All currents must be greater than zero, with an offset ranging between a 45° lag and a 15° lead (power factor > 0.7 inductive or > 0.96
capacitive)
Display check
WM15 verifies the connections and analyses the measured dimensions. In case of wiring errors it suggests the changes through a graphical
interface.
During operation, if a wiring error is detected the alarm icon will light up.
If the three conditions fail to be met, the following indications shall be displayed in the VOLTAGE CHECK and CURRENT CHECK pages:
• V MISSING: at least one voltage is missing
• I MISSING: at least one current is missing
• PF OUT OF RANGE: the current-voltage offset is out of range.
Check from UCS software or UCS Mobile
By connecting to WM15 through the UCS software or UCS Mobile, you can verify the connections and perform the steps required to correct
the wiring error.
Virtual correction from UCS software or UCS Mobile
The virtual correction function allows to calculate the wiring error solution and to modify the association of the physical connections with the
measurement references.
Example
if the connections of terminals 5 and 6 are inverted (voltage 2 and voltage 3), by accepting the proposed solution, voltage 2 shall be the one
measured with reference to terminal 6, while voltage 3 shall be the one referring to terminal 5.
The unit shall display the
icon, signalling that the association was modified via software and referring to the info pages to check the
phase-terminal associations set by UCS.
Note:
the function is not available in MID models
Summary of Contents for WM15
Page 1: ...WM15 Power analyser for three phase systems USER MANUAL ...
Page 25: ...WM15 Analizzatore di potenza per sistemi trifase MANUALE UTENTE ...
Page 49: ...WM15 Netzanalysator für Dreiphasensysteme BETRIEBSANLEITUNG ...
Page 73: ...WM15 Analyseur de puissance pour systèmes triphasés MANUEL D EMPLOI ...
Page 97: ...WM15 Analizador de potencia para sistemas trifásicos MANUAL DE USUARIO ...
Page 121: ...WM15 Effektanalyseinstrument til trefasede systemer BRUGERMANUAL ...
Page 145: ...WM15 用于三相系统的功率分析仪 用户手册 ...
Page 147: ...3 WM15 用户手册 CARLO GAVAZZI Controls SpA 维护和处理 22 测量问题 22 警报 22 通信问题 22 显示问题 22 ...
Page 169: ...WM15 三相系統用電力分析儀 使用者手冊 ...
Page 171: ...3 WM15 使用者手冊 CARLO GAVAZZI Controls SpA 維護與廢棄 22 度量問題 22 警報 22 通訊問題 22 顯示問題 22 ...