< Output frequency according to analog input voltage and its setting >
- Analog Input Start Frequency (C16) C16 specifies the start frequency of inverter when F01=1 as follows:
0:
Select Value in C12; 1: Select 0 Hz.
C16 determines the analog input frequency reference (D17) for any analog voltage input below C12.
- Analog Input Low-pass Filter Gain (C17)
C17 specifies the number of sampling of filter analog input to help reducing noise on signal
Function
Code
Mod.
add.
Description
Def
Min
Max
U.M
R/W
C10
0x060A
Analog Input Voltage Offset
0
-100
100
0.1%
R/W
C11
0x060B
Analog Input Voltage Gain
1000
0
2000
0.1%
R/W
C12
0x060C
Frequency at Minimum Analog Input
0
0
F03
0.1Hz
C13
0x060D
Frequency at Maximum Analog
Input
0
0
F03
0.1Hz
C14
0x060E
Minimum Analog Input Offset
0
0
1000
0.1%
C15
0x060F
Maximum Analog Input Offset
1000
0
1000
0.1%
C16
0x0610
Analog Input Start Frequency
0
0
1
-
C17
0x0611
Analog Input Low-pass Filter Gain
4
1
8
-
4.4
Protective functions
4.4.1
Current limitation
When the output current of the inverter exceeds the level specified by the current limiter (F26), the inverter
automatically manages its output frequency to prevent a stall and limit the output current. (Refer to the
paragraph 2.5.2 Instantaneous over-current limitation)
If F25 = 1, the current limiter is enabled only during constant speed operation. If F25 = 2, the current limiter
is enabled during both of acceleration and constant speed operation. Choose F25 = 1 if you need to run the