The table below lists functions that can be assigned to terminal [30A/B/C]. For simple explanations, the
examples shown below are all written for the normal logic (Active ON).
Function code data
Functions assigned
Symbol
Active ON
Active OFF
99
1099
Alarm output (for any alarm)
ALM
-
Alarm output -- ARM (Function code data = 99)
If any alarm presents on RVBS, the alarm output signal is ON.
Function
code
Mod.
add.
Description
Def
Min
Max
U.M.
R/W
E07
0x0107
Terminal [30A/B/C] Function
99
0
1099
-
R/W
4.3.3
Analog input setting - compressor application
RVBS supports the frequency command to source external analog voltage input port which allows 0V to 10V
by setting F01=1. The analog input is processed to be used for frequency reference following next parameters
setting: - Analog Input Voltage Offset (C10) C10 specifies real time editable offset factor for analog input
voltage. - Analog Input Voltage Gain (C11) C11 specifies real time editable gain factor for analog input voltage.
- Frequency at Minimum Analog Input (C12) When Frequency Command Source is set to the Analog input
(F01=1), this parameter determines the Analog input frequency reference (D17) at minimum analog input
voltage, 0 V. - Frequency at Maximum Analog Input (C13) When Frequency Command Source is set to the
terminal input (F01=1), this parameter determines the Analog input frequency reference (D17) at maximum
analog input voltage, 10 V.
- Minimum Analog Input Offset (C14) C14 specifies offsets the minimum analog input reference corresponding
to C12.
➢
Example: if set to 10%, minimum analog voltage value becomes 1 V.
- Maximum Analog Input Offset (C15) C15 specifies offsets the maximum analog input reference
corresponding to C13.
➢
Example: if set to 90%, maximum analog voltage value becomes 9V. For any reference above C15,
the inverter holds the value in C13.