background image

Output Module 4 x 20 Amp

G 3830 4445

User Manual

Brugermanual

CARLO GAVAZZI INDUSTRI A/S

Over Hadstenvej 40, DK-8370 Hadsten

Phone/Telefon: +45 89 60 61 00

Fax: +45 86 98 25 22

www.carlogavazzi.com/ac

Certified in accordance with ISO 9001

Kvalificeret i overensstemmelse med ISO 9001

MAN G38304445 rev. 10-03.08

1

5

-0

2

9

-2

1

4

4-channel receiver with 4 normally open contact outputs. Each output is
individually coded by means of the code programmer GAP 1605. For
changing the default setting, please refer to the datasheet on GAP 1605.

The outputs are normally OFF. When a transmitter coded to the selected
channel is activated, the output turns ON and remains ON until the
respective channel becomes deactivated. The default setting is such that
upon loss of Dupline® carrier all the outputs go OFF. If fail polarity is set
to 1, the relays will go on upon loss of carrier.
On the front of the module, it is possible mechanical to override each
relay.

The

LED’s

will

not

follow

manual

override.

The

manual override will be reset if Dupline or power is put off and on in min.
10 sec. Each relay is labled so it is possible to see the relays actual
status.

Note:

At delivery some of the relays might be ON due to transportation

bumps. To be sure that the relays are OFF, connect the module to power
and Dupline and transmit on channels A1-4 once.

Note

: Due to the construction with bistable relays, the module is intend-

ed for heating and light control only.

Mode of Operation

Wiring Diagram

21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Power

supply

D+

1

2

3

4

out

out

out          out

1

2

3

4

D-

Du line

®

Fieldbus

Installationbus

Dimensions

H8-housing