Carel RCEZ Series Quick Start Manual Download Page 1

RCEZS*

RCEZC*

 (RCEZ*)

 

-

 

Electronic Controller 

Dimensions (mm)

Panel mounting

 

Rear (with 2 quick-fit side brackets)

Fig. 1

Fig. 2

Fig. 3

RC

Technical specifications

power supply

 

230 Vac +10 /-15% 50/60 Hz

rated power 3.5 VA

inputs 

 

NTC or PTC probes 1 or 2 inputs. 
Digital input as alternative to third probe

relay outputs 

 

2 Hp relay      12 A Res. 12 FLA 72 LRA - 250 Vac(RCEZS*), 

 

 

             12 A Res. 10 FLA 60 LRA - 250 Vac(RCEZC*)

8 A relay        8 A Res. 2 FLA 12 LRA - 250 Vac

type of probe  Std CAREL NTC 10  K

Ω

 at 25 °C 

connections

 

Screw terminals for cables with cross-sect. from 0.5 mm   to 1.5 mm
Plug-in terminals for screw blocks or with crimped contact 
Rated maximum current per terminal 12 A.

2

2

assembly

 

Screws with rear brackets. 

display

3 digit LED display with sign (-199 to 999) and decimal point; six status LEDs

operating conditions

-10T50 °C - humidity <90% rH non-condensing

storage conditions

-20T70 °C - humidity <90% rH non-condensing

range of measurement

-50T90 °C  - resolution 0.1 °C

front panel index of protection

panel installation with IP65 type 1 gasket

case

plastic terminal, 81x26x65 mm

classification according to protec
-tion against electric shock

Class II when suitably integrated

environmental pollution

normal

PTI of the insulating material

250 V

period of stress across
 the insulating parts

long

category of resistance to heat and fire 

category D (UL94 - V2)

immunity against voltage surges category 1
type of action and disconnection 1C relay contacts
no. of relay automatic operating cycles 100,000 operations
software class and structure Class A
cleaning the instrument

Only use neutral detergents and water. 

cable max. lenght

probes: 30 m
relay: 10 m

WARNING:

do not run the power cable less than 3 cm from the bottom part of the device or 
from the probes;  

for the connections only use copper wires.

IMPORTANT WARNINGS:

The CAREL product is a state-of-the-art device, whose operation is specified in the technical
documentation supplied with the product or can be downloaded, even prior to purchase, 
from the website www.carel.com. 
The customer (manufacturer, developer or installer of the final equipment) accepts all liability
and risk relating to the configuration of the product in order to reach the expected results in 
relation to the specific final installation and/or equipment. The failure to complete such phase,
which is required/indicated in the user manual, may cause the final product to malfunction;  
CAREL accepts no liability in such cases. The customer must use the product only in the manner 
described in the documentation relating to the product. The liability of CAREL in relation to its 
products is specified in the CAREL general contract conditions, available on the website www.
carel.com and/or by specific agreements with customers. 

1     2   3    4    5

6   7

9 10  11

8

L

L

N

230VAC

NTC

PROBES

1    2    3    4    5

6   7

9 10  11

8

L

L

N

230VAC

DEF. T.

NTC

PROBES

Compressor

Compressor

Electrical connections

Disposal of the product
The appliance (or the product) must be disposed 
of separately in accordance with the local waste 
disposal legislation in force.

 

Fan

AMB.T.

Light

AMB.T.

Defrost

Reviews: