Carel PJS6 Quick Start Manual Download Page 1

+050004210- rel. 1.0 - 16.07.2013

Descrizione 

PJS6* rappresenta una gamma di regolatori elettronici a microprocessore con 
visualizzazione a LED realizzati per la gestione di unità frigorifere, vetrine e 
banchi frigo.

Caratteristiche tecniche

alimentazione (*)

230 Vac +10 /-15% 50/60 Hz; 115 Vac +10 /-15% 50/60 Hz
12 Vac +10/-15% 50/60 Hz classe 2;  12 Vdc +10/-20% classe 2

potenza nominale 3,5 VA
ingressi (*)

sonda NTC o PTC 1 o 3 ingressi
ingresso digitale in alternativa a terza sonda

uscite relè (*)

relè 2 Hp  

UL: 12 A Res. 12 FLA 72 LRA - 240 Vac (***), 

 

UL: 12 A Res. 10 FLA 60 LRA - 240 Vac (****)

 

EN60730-1: 10(10) A 250 Vac (**)

relè 16 A  

UL: 12 A Res. 5 FLA 30 LRA - 240 Vac C300, 

 

EN60730-1: 12(2) A NO/NC, 10(4) A fi no 60 °C NO, 

 

                      2(2) A CO - 250 Vac

relè 8 A  

UL: 8 A Res. 2 FLA 12 LRA - 240 Vac C300, 

 

EN60730-1: 8(4) A NO, 6(4) A NC, 2(2) A CO - 250 Vac

tipo di sonda (*)

NTC Std CAREL 10 KΩa 25 °C, PTC Std CAREL 985 Ω a 25 °C

connessioni (*)

- morsetti fi ssi a vite per cavi con sez. da 0,5 mm

2

 a 1,5 mm

2

            

- morsetti estraibili per blocchetti a vite o con contatto a 
  crimpare (sez. cavo fi no a 2,5 mm

2

). 

- corrente nominale massima per morsetto 12 A.

montaggio (*)

per terminale: mediante viti dal frontale o con staff e posteriori

visualizzazione

display LED 3 cifre con segno (-199…999) e punto decimale; 
sei LED di stato

condizioni di funzionamento

-10T50 °C - umidità <90% U.R. non condensante

condizioni di immagazzinamento

-20T70 °C - umidità <90% U.R. non condensante

intervallo di rilevazione

-50T90 °C (-58T194 °F) - risoluzione 0,1 °C/°F

grado di protezione frontale

montaggio a quadro con guarnizione: IP65 tipo 1

contenitore

terminale plastico, 81x36x65 mm

classifi c. secondo la protezione 
contro le scosse elettriche

classe II per incorporamento adeguato

inquinamento ambientale

normale

PTI dei materiali di isolamento

250 V

periodo delle sollecitazioni 
elettriche delle parti isolanti

lungo

categ. di resistenza al calore e al fuoco categoria D (UL94 - V0)
immunità contro le sovratensioni

categoria 1

tipo di azione e disconnessione

contatti relè 1C

n.ro di cicli di manovra delle 
operazioni automatiche relè (*)

EN60730-1: 100.000 operazioni
UL: 

30.000 operazioni (250 Vac)

classe e struttura del software

classe A

pulizia dello strumento

utilizzare esclusivamente detergenti neutri ed acqua

lunghezza max. cavi

seriale: 1 km, sonde: 30 m, relè: 10 m

Tab.  2

Avvertenza: 

non passare cavi di potenza a meno di 3 cm dalla parte inferiore del dispositivo o dalle sonde; per le 

connessioni usare solo cavi di rame. 

(*) Le caratteristiche indicate si diff erenziano a seconda del modello.  

(***) solo per i modelli PJS6 (M, S, X)* 

(**) T OFF minimo tra due start motore deve essere maggiore di 60 s.  

(****) solo per i modelli PJS6(C, Y)*

LED e funzioni associate

Icona Funzione

Normale funzionamento

Start up

ON

OFF

blink

compressore acceso

spento

richiesto ON

ventola

acceso

spento

richiesto ON

defrost

acceso

spento

richiesto ON

AUX

aux / heater

uscita accesa

uscita spenta

-

ON

allarme

tutti

nessun allarme

-

ON

orologio

RTC presente e 
abilitato, ed è stata 
impostata almeno 
una fascia oraria

RTC assente o disabilit.; 
oppure non è stata 
impostata nemmeno 
una fascia oraria

-

ON se RTC 
presente

Tab. 4

Tabella attivazione funzioni tramite i tasti 

Tasto

Normale funzionamento

Start up

pressione del singolo tasto
più di 3 s: alterna  stati ON/OFF

-

più di 3 s: attiva/disattiva defrost

Premuti 
insieme 
attivano 
procedura 
RESET 
parametri

per 1 s 
visualizza cod. 
vers. fi rmware

- 1 s.: visualizza/permette di impostare set point

per 1 s RESET 
banco EZY 
corrente

- più di 3 s: accesso menù impostazione parametri   
(inserire password ‘22’)
- Tacita allarme acustico (buzzer)

Tab. 5

Impostazioni del set point (valore di temperatura desiderato)

•  premere per 1 s SET, dopo alcuni istanti il valore impostato per St1 lampeggia;
•  aumentare o diminuire tale valore con UP o DOWN;
•  premere SET per confermare il nuovo valore.
Se abilitato il set point2 (H6=1), 
•  tenendo premuto SET, dopo alcuni istanti  il valore impostato per St2 lampeggia;
•  aumentare o diminuire tale valore con UP o DOWN;
•  premere SET per confermare il nuovo valore.

ON/OFF dello strumento

Premere per più di 3 s UP. In questa condizione gli algoritmi di regolazione e 
defrost sono disabilitati e lo strumento alterna la visualizzazione a display del 
messaggio “OFF” a quella della temperatura della sonda impostata.

Sbrinamento manuale

Premere per più di 3 s DOWN (si attiva solo se sussistono le condizioni di 
temperatura).

Accesso e modifi ca parametri tipo F (frequenti) e tipo C 
(confi gurazione)

1.  premere SET per 3 s (sul display comparirà “PS”);
2.  - per accedere al menù parametri di tipo F e C digitare la password “22” con 

UP/DOWN;
- per accedere solo al menù parametri F premere SET (senza digitare la password);

3.  navigare all’interno del menù parametri con UP/DOWN;
4.  per visualizzare/modifi care i valori del parametro visualizzato premere SET, 

quindi UP/DOWN ed infi ne SET per confermare la modifi ca (si ritorna così al 
menù dei parametri). 

Per salvare defi nitivamente tutti i valori modifi cati ed uscire dal menù parametri 
premere SET per 3 s;
Per uscire dal menù senza salvare i valori modifi cati (uscita per time out) non 
premere alcun tasto per almeno 60 s.

Dimensioni (mm) / Dimensions (mm)

71x29

10

3

33

74

81

36

58

65,29

28

.5

Montaggio a pannello / Panel mounting

Frontale (con 2 viti ø 2,5x12 mm) / Front (with 2 screws ø 2,5x12 mm)

max 2,5

1

2

3

Da dietro (con 2 staff e posteriori) / Rear (with 2 quick-fi t side brackets)

1

2

PUSH

Collegamenti elettrici / Electrical connections

1    2     3    4    5

6   7

9 10 11

8

L

L

N

230V~

-10T50

U

se c

opper c

onduc

tors only

Ref

. C614A233/R0

8(4)A 10(10)A                    EN60730-1

8A 2FLA 12LRA 12A 12FLA 72LRA   UL 873

  P2

   P1

NTC
PROBES

or

SERIAL

CONV

PROG.

KEY

DI / NT

C

AUX

250 Vac

OUT1

OUT2

1    2    3    4    5

6    7

9 10 11

8

L

L

N

U

se c

opper c

onduc

tors only

Ref

. C614A234/R1

8(4)A

10(10)A                    EN60730-1

8A 2FLA 12LRA

12A 10FLA 60LRA   UL 873

  P2

DI / NT

C

   P1

NTC
PROBES

or

SERIAL

CONV

PROG.

KEY

-10T50

250 Vac

230V~

OUT1

OUT2

OUT3

AUX

(*) Confi gurabile con VPM anche come FAN o SBRINAMENTO  / Can also be confi gured as 
FAN or DEFROST using VPM

controlli elettronici per la gestione di intervalli di temperatura /

 electronic controller for  range temperature management

PJS6

Tabella allarmi / Alarms table

Codice allarme Buzzer e relè allarme LED

Descrizione allarme

Parametri coinvolti

E0

attivi

ON

errore sonda 1

-

E1

non attivi

ON

errore sonda 2

[d0 = 0 / 1]

E2

non attivi

ON

errore sonda 3

[A4=10]

IA

attivi

ON

allarme esterno

[A4 = 1] [+A7]

dOr

attivi

ON

allarme porta aperta

[A4 = 7/8][+A7]

LO

attivi

ON

allarme bassa temperatura

[AL] [Ad]

HI

attivi

ON

allarme alta temperatura

[AH] [Ad]

EE

non attivi

ON

errore parametri macchina

-

EF

non attivi

ON

errore parametri funzionamento

-

Ed

non attivi

ON

defrost fi nito per timeout

[dP] [dt] [d4] [A8]

dF

non attivi

OFF

defrost in esecuzione

[d6=0]

EtC

non attivi

ON

allarme orologio

se fasce attive

Alarm code

buzzer and alarm relay LED

Description

Parameters involved

E0

active

ON

probe 1 error

-

E1

inactive

ON

probe 2 error

[d0 = 0 / 1]

E2

inactive

ON

probe 3 error

[A4=10]

IA

active

ON

external alarm

[A4 = 1] [+A7]

dOr

active

ON

open door alarm

[A4 = 7/8][+A7]

LO

active

ON

low temperature alarm

[AL] [Ad]

HI

active

ON

high temperature alarm

[AH] [Ad]

EE

inactive

ON

unit parameter error

-

EF

inactive

ON

operating parameter error

-

Ed

inactive

ON

defrost ended by timeout

[dP] [dt] [d4] [A8]

dF

inactive

OFF

defrost running

[d6=0]

EtC

inactive

ON

clock alarm

if bands active

Tab.  1

Description 

PJS6* is a range of electronic microprocessor controllers with LED display, 
designed to manage refrigeration units, showcases and cabinets.

Technical specifi cations

power supply  (*)

230 Vac +10 /-15% 50/60 Hz; 115 Vac +10 /-15% 50/60 Hz
12 Vac +10/-15% 50/60 Hz class 2;  12 Vdc +10/-20% class 2

rated power

3,5 VA

inputs (*)

NTC or PTC probes 1 or 3 inputs. 
Digital input as alternative to third probe

relay outputs (*)

relay 2 Hp   UL: 12 A Res. 12 FLA 72 LRA - 240 Vac (***), 
 

UL: 12 A Res. 10 FLA 60 LRA - 240 Vac (****)

 

EN60730-1: 10(10) A 250 Vac (**)

relay 16 A   UL: 12 A Res. 5 FLA 30 LRA - 240 Vac C300, 
 

EN60730-1: 12(2) A NO/NC, 10(4) A up to 60 °C NO, 

 

                      2(2) A CO - 250 Vac

relay 8 A  

UL: 8 A Res. 2 FLA 12 LRA - 240 Vac C300, 

 

EN60730-1: 8(4) A NO, 6(4) A NC, 2(2) A CO - 250 Vac

type of probe (*)

NTC Std CAREL 10 KΩa 25 °C, PTC Std CAREL 985 Ω a 25 °C

connections (*)

- screw terminals for cables with cross-sect. from 0.5 mm

2

 to 1.5 mm

2

.           

- Plug-in terminals for screw blocks or with crimped contact (cable  
   cross-sect. up to 2.5 mm

2

).  

- Rated maximum current per terminal 12 A.

assembly (*)

terminal: using screws from the front panel or with rear brackets.

display

3 digit LED display with sign (-199 to 999) and decimal point; 
six status LEDs

operating conditions

-10T50 °C - humidity <90% rH non-condensing

storage conditions

-20T70 °C - humidity <90% rH non-condensing

range of measurement

-50T90 °C (-58T194 °F) - resolution 0.1 °C/°F

front panel index of protection

panel installation with IP65 type 1 gasket

case

plastic terminal, 81x36x65 mm

front panel index of protection

class II when suitably integrated

environmental pollution

normal

PTI of the insulating material

250 V

period of stress across the insulating 
parts

long

category of resist. to heat and fi re

category D (UL94 - V0)

immunity against voltage surges

category 1

type of action and disconnection

1C relay contacts

no. of relay automatic operating 
cycles (*)

EN60730-1: 100.000 operations
UL: 

30.000 operations (250 Vac)

software class and structure

class A

cleaning the instrument

Only use neutral detergents and water.

cable max. lenght

serial: 1 km,  probes: 30 m,  relay: 10 m

Tab.  2

Warning: 

do not run the power cable less than 3 cm from the bottom part of the device or from the probes; for 

the connections only use copper wires.  

(*) The features indicated diff er according to the model.

(***) only for PJS6 (S, X)* models

(**) T OFF min. time between two starts of the motor must be greater than 60 s.

(****)  only for PJS6 (C, Y)*

LEDs and associated functions

Icon

Function

Normal operation

Start up

ON

OFF

blink

compressor

ON

OFF

request

ON

fan

ON

OFF

request

ON

defrost

ON

OFF

request

ON

AUX

aux / heater

output on

output off 

-

ON

alarm

all

no alarm

-

ON

clock

RTC fi tted and 
enabled, at least a 
time band set

RTC not fi tted or 
disabled, not even a 
time band set

-

ON if RTC 
fi tted

Tab. 4

Table of functions activated by the buttons 

Button

Normal operation

Start up

pressing the button alone
more than 3 s: toggle ON/OFF

-

more than 3 s: start/stop defrost

Pressed 
together start 
parameter 
RESET 
procedure

for 1 s display 
fi rmware vers. 
code

- 1 s.: display/set the set point

for 1 s RESET 
current EZY set

- more than 3 s: access parameter setting menu 
(enter password ‘22’)
- mute audible alarm (buzzer)

Tab. 5

Setting the set point (desired temperature value)

•  press SET for 1 s, after a few moments the value set for St1 fl ashes;
•  increase or decrease the value using UP or DOWN;
•  press SET to confi rm the new value.
If set point 2 is enabled (H6=1), 
•  press and hold SET, after a few moments the value set for St2 fl ashes;
•  increase or decrease this value using UP or DOWN;
•  press SET to confi rm the new value.

Switching the device ON/OFF

Press UP for more than 3 s. The control and defrost algorithms are now disabled 
and the instrument displays the message “OFF” alternating with the temperature 
read by the set probe.

Manual defrost

Press for DOWN more than 3 s (the defrost starts only the temperature conditions 
are valid)

Access and setting type F (frequent) and type C (confi guration) 
parameters

1.  press SET for 3 s (the display will show “PS”);
2.  - to access the type F and C parameter menu, enter the password “22” using 

UP/DOWN;
- to access the F parameter menu only, press SET (without entering the 
password);

3.  scroll inside the parameter menu using UP/DOWN;
4.  - to display/set the values of the parameter displayed, press SET, then UP/

DOWN and fi nally SET to confi rm the changes (returning to the parameter 
menu). 

To save all the new values and exit the parameter menu, press SET for 3 s;
To exit the menu without saving the changed values (exit by timeout) do not 
press any button for at least 60 s.

 Fig. 1

 Fig. 2

 Fig. 3

 Fig. 4

 Fig. 5

IMPORTANT WARNINGS: 

The CAREL product is a state-of-the-art product, whose operation is 

specifi ed in the technical documentation supplied with the product or can be downloaded, even prior 
to purchase, from the website www.carel.com.  -  The client (builder, developer or installer of the fi nal 
equipment) assumes every responsibility and risk relating to the phase of confi guration the product 
in order to reach the expected results in relation to the specifi c fi nal installation and/or equipment. 
The lack of such phase of study, which is requested/indicated in the user manual, can cause the fi nal 
product to malfunction of which CAREL can not be held responsible.   The fi nal client must use the 
product only in the manner described in the documentation related to the product itself.   The liability 
of CAREL in relation to its own product is regulated by CAREL’s general contract conditions edited on the 
website www.carel.com and/or by specifi c agreements with clients.

NO POWER 

& SIGNAL 

CABLES 

TOGETHER

READ CAREFULLY IN THE TEXT!

WARNING: 

separate as much as possible the probe and digital input signal cables from the cables 

carrying inductive loads and power cables to avoid possible electromagnetic disturbance. Never run 
power cables (including the electrical panel wiring) and signal cables in the same conduits.

DISPOSAL OF THE PRODUCT: 

The appliance (or the product) must be disposed of separately in 

accordance with the local waste disposal legislation in force.

NORMATIVE DI SICUREZZA - 

conforme alle Normative europee in materia. 

Precauzioni d’installazione:
•  i cavi di collegamento devono garantire l’isolamento fi no a 90 °C;
•  per le versioni 12 Vac utilizzare trasformatori Classe II. Per il rispetto delle normative EN 61000-4-4, EN 61000-4-5, EN 61000-4-11, 

EN 61000-4-6, EN 60730-1, il trasformatore deve essere uno dei modelli indicati (vedi Listino Prezzi CAREL). Per le versioni 12 Vac/
dc, non essendo possibile garantire il doppio isolamento tra i connettori di alimentazione e le uscite relè, si raccomanda di utilizzare 
carichi alimentati solamente in bassissima tensione di sicurezza (fi no a 42 V nominali di valore effi  cace);

•  prevedere almeno 10 mm di distanza tra il contenitore e parti conduttive vicine;
•  collegamenti degli ingressi digitali e analogici inferiori a 30 m di distanza; adottare le adeguate misure di separazione dei cavi 

per il rispetto delle normative suddette.

•  Bloccare  bene i cavi di connessione delle uscite per evitare contatti con parti in bassissima tensione di sicurezza

.

SAFETY STANDARDS - 

compliant with the relevant European standards. 

Installation precautions:
•  the connection cables must guarantee insulation up to 90 °C;
•  for 12 Vac versions use Class II transformers. To ensure compliance with the immunity standards (surge), the transformer must 

be one of the models specifi ed (see the CAREL price list). For the 12 Vac/dc versions, as double insulation cannot be guaranteed 
between the power supply and the relay outputs, only use safety low voltage loads (up to 42 V eff ective rated value);

•  ensure a space of at least 10 mm between the case and the nearby conductive parts;
•  digital and analogue input connections less than 30 m away; adopt suitable measures for separating the cables so as to ensure 

compliance with the immunity standards;

•  Secure the connection cables of the outputs so as to avoid contact with very low voltage parts.

(*)

VPM: visual parameter manager in http://ksa.carel.com -  VPM: visual parameter manager 
at http://ksa.carel.com