IROPZ48500: 

RS485 serial board interface option for IR33/powercompact

cod. +050003880 - rel. 1.1 - 07/11/2008

CAREL S.p.A.  

Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 0499716611  –   Fax (+39) 0499716600
http://www.carel.com – e-mail: [email protected]

CAREL si riserva la possibilità di apportare modifiche o cambiamenti ai propri prodotti senza alcun preavviso.

CAREL reserves the right to modify the features of its products without prior notice.

cod. +050003880 - rel. 1.1 - 07/11/2008

Thank you for your choice. We trust you will be satisfied with your 
purchase.

The RS485 serial option is used to connect CAREL compatible  
controllers to a supervisory network via a standard RS485 serial line. The 
input normally used for the programming key is also used for this pur-
pose, having the dual function of key input / serial communication port 
(only on controllers where fitted).

Assembly

Connect the RS485 option to the CAREL controllers (at the key serial 
input) using the 4-wire cable; depending on the neccessity use a cable 
75mm or 220mm lenght. 
Make the connection to the supervisory network, as shown in Fig. 2. 
The serial line should be terminated with a 1/4 W 120 

Ω

 resistor between 

terminals TxRx+ and TxRx-.
Refer to the documents on the corresponding controllers for the  
setting of the serial address and the maximum number of connections.

WARNING: 
• Check the technical documents on the corresponding controllers for    
  the connection of the power supply, so as to avoid damaging the  

 

 instrument.
• Securely fasten the option so as to prevent it from being    

 

  disconnected. It must be fixed inside the same device as the  

 

 controller.
• Connect the wiring with the power supply disconnected.
• Keep the serial option cables separate from the power cables (relay    
  and power supply outputs).

Technical specifications

Power supply  

5 V ± 10%

(supplied by the controller)  
Storage conditions  

temperature –10T70°C;    

 

 

humidity 0% to 80% r.H., non-cond.

Operating conditions  

temperature –10T65°C;    

 

 

humidity 20% to 80% r.H., non-cond.

Index of protection  

IP20

Environmental pollution 

normal

Protection against  

To be incorporated in class I or  

electric shock 

II devices.

 

The insulation depends on the  

 

 

controller the option is connected to.

Category of resistance  

D (UL94 HB)

to heat and fire 
PTI of the insulating  

250 V

materials
3-way terminal 

cross-section 1.5 mm

2

Cables to be used 

twisted pair plus shield 

Serial port 

not optically-isolated

Speed 19200 

baud

Maximum distance from   

1 km

the supervisor 

24

31

54

85 / 230

75 / 220

5

5

GND
T+
T-

GND

T+
T-

GN

D

T+

T-

PC485KIT00

1..

powercompact

IR33

...n

GND

USB-485
Converter

CVSTDUMOR0

T+

T -

USB

SERIAL PORT

Dimensions

Fig. 1

Connection example

Fig. 2