Page 26
11. Advanced settings
To Set Up Advanced Settings:
Menu-Nr. 4
Add photocell
(Only E-King photocell which is an optional accessory)
Operator is in normal operating mode.
1.
Press P for 5 seconds until Nr. 4 blinks.
2.
Release P when Nr. 4 blinks.
3.
A. Press + if a photocell is to be installed (Nr. 2 flashes)
B. Press - if no photocell is to be installed (Nr. 1 flashes)
4.
Press P to store settings and to go to Menu-Nr. 5.
Menu-Nr. 5
Set maximum opening force
Attention:
The automatic cut-out is set automatically. Only change it if necessary (error No. 10).
Always test the max. allowed operating forces according to EN 12445 and EN 12453!
Advice:
The setting of the automatic cut-out corresponds to the maximum power of the operator. At the first travel
to OPEN or CLOSE direction after 'POWER ON' the automatic cut-out is effective according to the adjust-
ment. For further travels the self-learned power, that is more sensitive, is effective.
The automatic cut-out is still the upper limit of power.
1.
Nr. 5 blinks.
2.
By pr and - set the desired maximum lifting force.
Possible Settings:
3.
Once maximum opening force is set press P to store and go to Menu-Nr. 6.
Attention:
When re-programming the end positions (basic settings) the opening force is learned once more.
With new setting of the end positions the force values are determined automatically. Depending on the door
travel properties increasing of the force values may be necessary.
Page 19
9.
Progamming
9.5
Function test
Test run of the maximum required lifting force
Control:
After installing the operator the following test runs and checks must be carried out.
After setting the end positions, the operator adopts the maximum required lifting force during the first two runs.
• Run the operator (with coupled door) without interruptions:
1 x from the CLOSED end position to the OPEN end position and back.
During this test run, the operator determines the maximum opening and closing lifting force as well as the reserve
power (offset value) which is required to move the door
Advice:
These settings remain unchanged even if power supply is interrupted. The maximum required OPEN and
CLOSE lifting force reverts back to the factory default settings only when the reset button is pressed.