Page 14
9.2
Programming Overview
9.
Progamming
Basic Settings
1. Programming 'door open' position
2. Programming 'door closed' position
3. Programming of hand transmitter code
Advanced Settings part 1
Explanation
Factory settings
Add photocell (beam break)
Setting whether the operator runs with or without photocell
1 = No
Set maximum opening force
The maximum lifting force (linear line)
8
Set maximum closing force
The maximum push force (linear line)
8
Set offset (sensitivity) for learned
opening force
The sensitivity of learned opening force
7
Set offset (sensitivity) for learned
closing force
The sensitivity of learned closing force
7
Set operator speed up
The operator speed in opening direction
16 = 16/16
Set operator speed down
The operator speed in closing direction
16 = 16/16
Set soft stop
The soft stop before closing the door
2 = 200mm
Automatic closing
Door open period set at 30sec. / 1sec. warning / external signal
light blinking.
1 = off
Set start-up warning phase before
door opens
Setting whether a signal light will flash before the door starts to
move in opening direction
1 = deactivated
Set external relay function
The external optional relay can be programmed for external
blinking or illuminated signal light
1 = GDO run solid
Page 31
11. Advanced settings
Menu-Nr. 18
Set external relay function
1.
Nr. 18 blinks.
2.
Use + or - to set the signal light function
Possible Settings:
A
Illuminated during motor movement
B
Blinking during operator movement
C
Illuminated as internal operator light (timed)
D
Short impulse output (1 sec.)
E
Illuminated while Error with operator
F
Break-in alarm function warning (only when backdrive of motor detected)
G
Relay on when door closed position is reached
H
Relay is on when door open position is reached
3.
Press P to store and to finish setting up the advanced settings part 1.
The operator is now in operational (normal) mode.
A
B
C
D
E
F
G
H