4.0 Adjustment Procedure 

4.1 Zero point adjustment in stationary 

 

medium: Adjust potentiometer P2 after 

 

5 minutes so that Ia = 4 mA. 
i.e. if Ia > 4 mA turn pot. P2 slowly to the left 
      if Ia < 4 mA turn pot. P2 sowIy to the right. 

4.2 Adjustment of measurement range at the max. flow rate 

which is to correspond to 20 mA output: After 3 minutes at max. flow-rate turn 
pot. P1 until Ia = 20 mA. 
i.e. if Ia > 20 mA turn pot. Pl slowly to the right 
     if: Ia < 20 mA turn pot. P1 slowly to the left. 

4.3 Check Zero Point and Range 

Check zero and range adjustments as in points 4.1 and 4.2 and correct any 

discrepancies as necessary. 

4.4 

LED indicates operation within measurement range, and switches oft when 

flow speed is out ot the adjusted range (Ia>2OmA). 