25
Building to Unit Power Wiring Connection
Figure 14 - Conduit Termination/Disconnect Switch Wiring
Site Preparation – Controls
• Consider general service and installation space when locating the remote temperature control.
• Locate the control as close to the space/fan that it will serve to reduce long, unnecessary wire runs.
• Install thermostats in locations that will produce a good representation of the air being moved by the
fan in the space. Avoid thermostat installations in direct sunlight, near HVAC supplies, or abnormal
temperature airstreams.
BK
BK
BK
BK
BK
BK
GR
208/460/600 V 3 PH.
Size 3 Unit Shown
Safety
Disconnect
Switch
Main Power to Unit’s
Safety Disconnect Switch
from Building Breaker
First Shelf
Run Conduit
to First Shelf
After Wiring Installation is
Complete, Seal All Base
Penetrations with
Appropriate Filler
Safety
Disconnect
Switch
Gal-flex
Conduit
Field Supplied
Wiring
Fused Disconnect Option
Fused Disconnect Options
250V
480/600V
Size
30A
60A
100A
DG321NRB
DG322NRB
DG323NRB
DG321NRB
DG322NRB
DG323NRB
1
1, 2, 3
1, 2, 3