Capstone Turbine Corporation
Model C65 Hybrid UPS User’s Manual
400027 Rev A (July 2010)
Page
39 of 66
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Display Panel Menu
Hierarchy – Typical
System State
UPS/EFF/EMER
kW In/kW Out
Clear Incident
High Incident,
Fault <Yes/No>
System
Configuration
Power Connect
<Options>
Multipac
<Enable/Disable>
Turbine No.
<Number>
Auto Restart
<Yes/No>
System Demand
<kW>
Control Access
<Device>
Logoff
<Yes/No>
Voltage
<Vrms>
Under Voltage
<Vrms>
<Sec>
Over Voltage
<Vrms>
<Sec>
Under Voltage
<Vrms>
<Sec>
Over Voltage
<Vrms>
<Sec>
Fast Under Vltg
<Vrms>
<Sec>
Fast Over Vltg
<Vrms>
<Sec>
Under Frequency
<Hz>
<Sec>
Over Frequency
<Hz>
<Sec>
Frequency
<Hz>
Under Frequency
<Hz>
<Sec>
Over Frequency
<Hz>
<Sec>
MP Min Power
<kW>
<Sec>
Engine State
Fault Status
Utility kW
Load kW
Utility Freq
Load Freq
Utility Volts A
Load Volts A
Utility Volts B
Load Volts B
Utility Volts C
Load Volts C
TET
RPM
Fuel Pressure
Fuel %
Battery Voltage
Battery Current
Batt SOC
Last EQ charge
Temp C/F
C65 Main code
Version
CHP Wtr In Tmp
CHP Wtr Out
Tmp
CHP Temp Fdbk
Hours
Starts
Reboot
<Yes/No>
Enter Password
<Password>
Reconnect DLY
<Min>
Clear Fuel Fault
<Yes/No>
System Data
Utility Input
Load Output
Unit Data
Legend:
Unbold boxes signify data display only.
Bold boxes signify User password is required to change the value
or parameter.
Dashed boxes signify settings that can only be changed by an
Authorized Service Provider using CRMS.
Utility Amps A
Load Amps A
Utility Amps B
Load Amps B
Utility Amps C
Load Amps C
Engine State
LOAD/STB
kW Gen
MT Start Delay
<Min>
Local Batt Chg
<Enable/
Disable>
System State
Fault Status
Figure 7. Display Panel Menu Reflecting Function Hierarchy