The following table shows different behaviours with different warm-up values: 

Warm-Up value 

Effetto 

The device doesn

t generate any voltage but, in any case, carries out the measurements. 

>=1 

<=32 

The  device  generates  a  voltage  for  a  period  in  seconds  equal  to  the  value  inserted  +450ms 
(

approximately

). 

>32 

The  device  sets-up  the  warm-up  time  to  32s  and  generates  a  voltage  for  a  period  of 
approximately 32.45s.  

Decimal value 

The device round down the inserted value. 

<0 

The  device  sets-up  the  warm-up  time  to  32s  and  generates  a  voltage  for  a  period  of 
approximately 32.45s. 

 

Save the new configuration clicking on 

Write

 button.  

7.

 

Device pre-set and use mode. 

a.

 

Wireless Mode:  

No setup operation is needed. Typically, the system is configured in factory, so the device is already associated to the system gateway. The 
device is in STANDBY mode (

refer to

 

Picture 7 - Command table

for which is necessary to start it with the TEST command (

refer to

 

10 - Installation 

procedure.

).  

Otherwise, in case the device is in FACTORY RESET mode (

refer to

 

Picture 7 - Command table

), that means it's ready for connecting to an existing 

system, in order to associate it, make reference to the 

WineCap System - User Manual R30

 

software manual. It is necessary to use the 

WineCapManager 

software on the PC connected to the gateway that will be linked with the device.  

b.

 

USB Logger Mode: 

For this operation mode, stand-alone with data downloads through USB, the connection with the PC and the 

WineCapManager

 running on it 

is necessary to modify the device 's operation mode. The sampling interval must be set with the device in STAND-ALONE 

(

refer to

 

11 - Stand-

alone USB datalogger installation.

mode  and  automatically,  the  device  's  clock  is  aligned  with  the  PC's  clock,  in  order  to  assure  the  temporal 

reference of the sample. 

Sampling operations start may be selected disconnecting the USB cable or giving the proper command with the magnetic key (

refer to

 

11 - 

Stand-alone USB datalogger installation.

). More details on device 's connection/disconnection through the USB cable are available on the 

WineCap 

System - User Manual R30

 

manual. 

c.

 

On field transition from USB to Wireless datalogger: 

This transition is practicable in field, during the sampling period, using the wireless network association command. When the association is 
done, the datalogger becomes a wireless datalogger and, besides sending new measures to the gateway, starts a download process towards 
the same gateway of the measures acquired during the stand-alone period (

refer t

Picture 9 - Stand-alone device - Status table

). 

 

 

Summary of Contents for WSD12PS-4AI

Page 1: ...WSD12PS 4AI User Manual ...

Page 2: ...p to 100mA distributed on 4 analog channels Measurements acquired are expressed in percentage of full scale 2 Channel description Picture 1 Product image SHIELD shield cable connection PS INPUT datalogger generated voltage negative pole Input signal negative reference INPUT Signal input 0 25mA 0 5Vdc 0 10Vdc 0 25Vdc Full scale selectable using scale jumpers PS datalogger generated voltage positive...

Page 3: ...c 100mA default Picture 3 Jumper positions Removing jumper J10 Errore L origine riferimento non è stata trovata voltage generation on pin PS of the terminal block is disabled This situation may be useful in case the DC voltage is not necessary Consequently the battery life is increased 4 Full scale setting The measurement s full scale selection is done positioning a jumper on the proper strip 0 25...

Page 4: ...PS 4AI can be programmed using WineCapManager to supply a warm up time variable from 1 default to 32 seconds Be sure that the device is linked to its gateway refer to 10 Installation procedure Run WineCapManager and open the plant related database If the database doesn t exist and the gateway is not properly licensed on connected PC refer to WineCap System User Manual R30 From the WineCapManager m...

Page 5: ...ww capetti it Click on InfoReq button Select the card Calibration Modify the Zero field with the desired warm up value default 1 maximum 32 The inserted value is expressed in seconds and represents the duration of output power supplied to transducer net off 0 4s of tolerance ...

Page 6: ...ociate it make reference to the WineCap System User Manual R30 software manual It is necessary to use the WineCapManager software on the PC connected to the gateway that will be linked with the device b USB Logger Mode For this operation mode stand alone with data downloads through USB the connection with the PC and the WineCapManager running on it is necessary to modify the device s operation mod...

Page 7: ...flashes STANDBY Temporary device deactivation the device is stopped The sampling process and the radio are is turned off losing the connection to the network To reactivate a TEST command is necessary The STANDBY command must be given twice to confirm it at the first sequence the led flashes alternating RED and GREEN lights waiting for the second confirm sequence within 15 seconds At the command ex...

Page 8: ...TUS RADIO SIGNAL QUALITY 5 green flashes ACTIVE Radio signal Excellent 4 green flashes ACTIVE Radio signal Good 3 green flashes ACTIVE Radio signal Fair 2 amber flashes ACTIVE Radio signal Sufficient 1 red flash ACTIVE Radio signal Insufficient 1 red flash 2 long OUT OF RANGE Network searching 2 red flashes 2 long STANDBY Radio off No Logging Short long short red flashes series FACTORY RESET Devic...

Page 9: ...time you can issue the STANDBY command refer to Picture 7 Command table It corresponds to the command number 4 and must be issued twice to confirm the operation Position the WineCapKey in the spot indicated in Picture 6 WineCapKey positioning and wait for four AMBER flashes then remove the WineCapKey from device Verify that the device asks for confirmation of STANDBY command with alternate GREEN R...

Page 10: ... up to 100mA Selectable onboard using jumpers Warm up time From 1 default to 32 seconds Selectable using WineCapManager Sampling interval Selectable from one minute to 24 hours 60 minutes default Datalogger capacity 64 000 samples for each channel Working temperature Operative 30 C 60 C Warehousing 40 C 70 C Radio frequency ISM 868MHz Radio coverage Up to 6Km in line of sight can be extended using...

Page 11: ...ion voltage measures on distances exceed 15 20 meters are subjected to electromagnetic disturbances 0 25mA inputs have a superior electromagnetic compatibility EMC Avoid passage in cavities with power or high voltage cables The protection and safety measures and the warranty provided by the Manufacturer with the equipment may be compromised if it s used in a manner that does not comply with this u...

Page 12: ...nic devices The WEEE logo on the label indicates that this product is compliant with the WEEE EC Directive This symbol valid only in the European Union countries indicates that the product it is applied to MUST NOT be discarded with ordinary household or industrial waste but must be sent to an authorized reception point The end user should contact the device provider either the manufacturer or the...

Reviews: