CDE360 Vector Control AC Drive Chapter 5 Parameter List Table
-
49
-
Function
Code
Name
Range
Default
Step
Description
A0.59
Motor temperature
0.0~300.0
0.0
0.1
℃
This value is from
PT100/PT1000
optional card.
A0.60
Inverter module temperature
-40.0~125.0
0.0
0.1
℃
A0.61
Rectifier module temperature
-40.0~125.0
0.0
0.1
℃
A1 Fault & Diagnostics
Function
Code
Name
Range
Default
Step
Description
A1.00
1st(latest) fault type
0~54
0
1
0: No fault
1: Hardware over voltage during acceleration
2: Hardware over voltage during deceleration
3: Hardware over voltage during constant speed
4: Software over voltage during acceleration
5: Software over voltage during deceleration
6: Software over voltage during constant speed
7: Under voltage
8: Hardware over current during acceleration
9: Hardware over current during deceleration
10: Hardware over current during constant speed
11: Software over current during acceleration
12: Software over current during deceleration
13: Software over current during constant speed
14: IGBT saturation trip during acceleration
15: IGBT saturation trip during deceleration
16: IGBT saturation trip during constant speed
17: Heatsink of rectifier overheat
18: Heatsink of inverter overheat
19: Input phase loss
20: Output phase loss
21: Soft-startup resistor fault
22: Current detection fault
23: CBC fault
24: AC drive over load
25: Motor overload
26: Motor underload
27: Motor overheat
28: Motor shortcircuit to ground fault
29: External fault
30: Keypad communication fault
31: RS485 communication fault
32: Optional card communication fault
33: Optional card connection fault
34: Auto tune fault
35: PID feedback over range
36: EEPROM R/W fault
37: Parameter setting fault
38: Accumulative power-on time reached
39: Accumulative running time reached
40: Motor switchover during running status
41: Too large speed deviation
42: Motor over-speed
43: Flux pole detection fail
44: UVW signal feedback fault
45: Encoder fault
46: User-defined fault 1
47: User-defined fault 2
48: Motor in current stall status
49: Motor in voltage stall status
50: Motor in frequency drop status as DC bus
voltage drop
51: System fault
52: Interlock warning during multi-pump operation
53: Soft start current limiting resistor overload
54: Sleep status