background image

SDM-CD16D 16 Channel Digital Control Port Expansion Module

2

2.2  Output Specifications

Output Voltage (no load):

  Output ON/HI, Nominal 5V (Minimum 4.5V)

Output OFF/LO, Nominal 0V (Maximum 0.1V)

Output Sink Current:

 

Output will sink 8.6mA from a 5V source*

Output Source Current:

 

Output will source 36mA @ 3V,
115mA short-circuited to ground*

Max. Output Current:

 

400mA at 50°C and 12V supply (see NOTE below)

(total all outputs)

The maximum current should be derated under the following
conditions:
50mA for every 10°C above 50°C and/or 50mA for every volt
above 12V. 

Operating temp.:

 -25

°

C to +70

°

C standard

Size:

230mm wide x 100mm high x 24mm deep

Weight:

350g

EMC Status:

Complies with EN55022-1:1998 and
EN50082-1:1998

*  If more detailed output characteristics are required, experienced users should consult the

equivalent circuit diagrams shown in Figure 2, below.

Figure 2  Equivalent Output Driver Circuit

3.  Power Considerations

The SDM-CD16D power requirements are large compared to most Campbell
Scientific products when driving significant loads. For many applications an
external power supply, as shown in Figure 3, is recommended to power the
SDM-CD16D.

For some applications it may be convenient to use the datalogger supply to power
the SDM-CD16D, as shown in Figure 3. For long-term applications, the lead-acid
power supply available with Campbell Scientific dataloggers should be used,
allowing the batteries to be float charged. Alkaline batteries are 

not

 recommended

for long term applications.

NOTE

0.6V Drop

Output

Output

580R

Output set ON/HI

Output set OFF/LO

510R

39R

V

5V, 0

Summary of Contents for SDM-CD16D

Page 1: ...SDM CD16D 16 Channel Digital Control Port Expansion Module User Guide Issued 15 6 99 Copyright 1999 Campbell Scientific Ltd...

Page 2: ......

Page 3: ...in lieu of all other guarantees expressed or implied including those of suitability and fitness for a particular purpose Campbell Scientific is not liable for consequential damage Please inform us bef...

Page 4: ......

Page 5: ...ddress Selection Switches 5 6 Datalogger Instructions 104 CR10 10X CR23X 21X newer CR7s and 29 older CR7s 6 7 Theory of Operation 7 8 Program Example 7 Figures 1 SDM CD16D 1 2 Equivalent Output Driver...

Page 6: ......

Page 7: ...nchronously addressed datalogger peripheral Datalogger control ports 1 2 and 3 are used to address the SDM CD16D then clock out the desired state of each of the 16 control ports Up to sixteen SDM CD16...

Page 8: ...d EN50082 1 1998 If more detailed output characteristics are required experienced users should consult the equivalent circuit diagrams shown in Figure 2 below Figure 2 Equivalent Output Driver Circuit...

Page 9: ...ls This limitation reduces the number of available analogue input channels and may make an external supply for the SDM CD16D essential 4 Installation For correct operation the SDM CD16D must be instal...

Page 10: ...ng SDM CD16Ds to SDM CD16Ds and the datalogger should not exceed 6m Total cable lengths in excess of 6m will adversely affect communication performance For CR7 dataloggers the total cable length can b...

Page 11: ...nding address Figures 1 and 5 shows the position of the switch Note that you will have to remove the mounting bracket to gain access to this switch Table 2 Switch Position and Addresses Switch Setting...

Page 12: ...tarting Address base 4 00 33 4 2 Card Excitation card No 5 4 Starting Input Location Execution Time 150ms to 190ms per Rep The number of SDM CD16Ds to be addressed is defined by the Reps repetitions p...

Page 13: ...controls output 1 When the 16 control bits are clocked in C2 is held high while C3 is pulsed low then high to latch the control bits The datalogger then lowers both C3 and C2 to complete the cycle 8 P...

Page 14: ...hreshold 2 4 3 23 5 F 4 30 Then Do then 3 Z F P30 put a 1 into heater control 1 1 F location 2 0 Exponent of 10 3 10 Z Loc Heat_1 4 End P95 end then do 5 If X F P89 if the heater is on heater 1 10 X L...

Page 15: ...hen Do 17 Z F P30 if cooler should be turned off 1 0 F put a 0 into cooler control 2 0 Exponent of 1 location 3 15 Z Loc Cool_1 18 End P95 end then do 19 Else P94 else if cooler is off 20 Z F P30 put...

Page 16: ...flag 2 is set 1 12 Do if Flag 2 is High 2 30 Then Do then 33 Beginning of Loop P87 start fan loop 1 0 Delay 2 5 Loop Count 34 Z F P30 put a 1 into fan control 1 1 F location 2 0 Exponent of 10 3 20 Z...

Page 17: ...3 3 11 Heat_2 11 1 0 12 Heat_3 11 1 0 13 Heat_4 11 1 0 14 Heat_5 19 1 0 15 Cool_1 7 3 3 16 Cool_2 11 1 0 17 Cool_3 11 1 0 18 Cool_4 11 1 0 19 Cool_5 19 1 0 20 Fan_1 7 1 3 21 Fan_2 11 1 0 22 Fan_3 11 1...

Reviews: