Campbell Nor150 Setup Manual Download Page 1

 

 

 

 

How to configure your Nor150 settings for Noise Nuisance Recording 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for Nor150

Page 1: ...How to configure your Nor150 settings for Noise Nuisance Recording ...

Page 2: ...First we need a template setup file you must load the Default setup first ...

Page 3: ...Press SETUP Key to start adjusting your settings for noise nuisance settings ...

Page 4: ...Set the Measurement Settings Set the Global Time measurement duration to 7 days ...

Page 5: ...Set the Profile A to 1 second resolution ...

Page 6: ...Set the frequency weighting Network A at least ...

Page 7: ...Set one 90 percentile to ...

Page 8: ...Adjust the functions like so LAeq G PA are the minimum requirement ...

Page 9: ...Set the audio recording settings ...

Page 10: ...surements of 7 days until you press STOP Automatic Automatic stop and save of the measurement duration 7 days Synchronised Measurements are saved into hourly periods 12 00 13 00 13 00 14 00 14 00 15 00 and so on Manual Manual stop and save of the measurement ...

Page 11: ...You can set your meter to display a 3 second countdown after pressing the Start button ...

Page 12: ...How to set a hand switch to record audio Set events 1 ON Configure your audio parameters Max Action Time Audio Recording Length ...

Page 13: ...Set a reference tone marker at 70dB ...

Page 14: ...Turn ON battery markers and event markers ...

Page 15: ...Reduce the number of views in the main measurement display to just one view Level v Time Level vs Time Level vs Frequecny SLM Noise Levels Only ...

Page 16: ...Configure Your Instrument Enable the hand switch by changing Outputs 1 4 to Recording S1 ...

Page 17: ...Set the headphones to Playback and adjust the volume as required ...

Page 18: ...Set the Reference Tone ...

Page 19: ...Configure the level vs time screen main window Press and hold the touch screen in the measurement window Select Functions Set Max Functions In View Turn of 2nd 3rd Functions ...

Page 20: ... Set the zoom range of screen Set the time unit to absolute displays current the date and time To do this press and hold your finger on the screen to display the menu ...

Page 21: ...Check everything works okay by starting a measurement and testing the hand switch lights up Press the X button to clear the screen Go to SETUP menu and save the measurement setup file ...

Page 22: ...Save the measurement in the memory You may write protect the setup but note you will not be able to change this later without saving the setup again as a new file name ...

Page 23: ...COMPLETE Now go back to applications Make sure the hide button is shown at the bottom of the screen Now load up your setup icon to test it out ...

Page 24: ... Chelmsford Road Industrial Estate Great Dunmow Essex CM6 1HD Tel 44 0 1371 871030 Fax 44 0 1371 879106 Www Campbell Associates Co Uk Company Registered In England Number 03700715 Registered Office 12 Alma Square Scarborough North Yorks YO11 1JU ...