3. On the CS I/O tab:
a. Set Configuration to PakBus.
b. Set SDC address. (Note that if multiple peripherals are connected to a data logger
CS I/O port, each must have a unique SDC address.)
c. Set Beacon Interval, Verify Interval, and PakBus Neighbors Allowed as described
above. Often, the default values can be used. However, an allowed neighbors list can
be useful in restricting communications paths.
4. On the Network Services tab, make note of the PakBus/TCP Service Port. (The default
PakBus/TCP Service Port is 6785. Unless firewall issues exist, it is not necessary to change
the port from its default value.)
8.2.1.3
LoggerNet
setup
1. In the
LoggerNet
Setup screen, click Add Root and select IPPort. Enter the NL241 IP address
and port number. The IP address and port number are input on the same line separated by
a colon.
2. Add a PakBus Port (PakBusPort).
3. Add a PakBus Router (pbRouter). Type the PakBus address of the NL241. The NL241 default
PakBus address is 678.
4. Add the data logger and type the PakBus address of the data logger.
5. Click Apply to save the changes.
FIGURE 8-1. PakBus router LoggerNet setup
NL241 Wireless Network Link Interface
27