Model HC2S3 Temperature and Relative Humidity Probe
8
TABLE 7-1. Wire Color, Function, and Datalogger Connection for
Single-Ended Measurement
Wire
Color
Wire Function
Datalogger Connection Terminal
Brown
Temperature
signal
U
configured for single-ended analog input
1
,
SE
(single-ended, analog-voltage input)
White
Relative
humidity signal
U
configured for single-ended analog input,
SE
Yellow
Signal reference
⏚
(analog ground)
Gray
Power ground
⏚
Clear
Shield
⏚
Green
Power
12V
or
SW12V
1
U channels are automatically configured by the measurement instruction.
When measuring the HC2S3 with single-ended
measurements, the yellow and gray leads must both be
connected to
⏚
on the datalogger. Doing otherwise will
connect the datalogger’s analog and power ground planes
to each other, which in some cases can cause offsets on
low-level analog measurements. To avoid 2 mA flowing into
analog ground, switch power on/off for its measurement.
TABLE 7-2. Wire Color, Function, and Datalogger Connection for
Differential Measurement
Wire Color
Wire Function
Datalogger Connection Terminal
Brown
Temperature signal
U
configured for differential
analog input H
1
,
Diff H
Jumper to
Yellow
Temperature signal
reference
U
configured for differential
analog input L,
Diff L
White
Relative humidity
signal
U
configured for differential
analog input H,
Diff H
Yellow
Signal reference
U
configured for differential
analog input L,
Diff L
Gray
Power ground
G
Clear
Shield
⏚
Green
Power
12V
or
SW12V
1
U channels are automatically configured by the measurement instruction.
CAUTION