Appendix A. Info Tables and Settings
634
PakBus
EncryptionKey
String
•
Settings Editor:
Datalogger | PakBus Encryption Key
Encryption key; 0 to 63 characters
PakBusNodes
Discontinued; aliased to
CommsMemAlloc
PakBusPort
Numeric Y
•
Settings Editor:
Network Services | PakBus/TCP Service Port
Specifies the TCP service port for PakBus communications if the PPP service is enabled.
Unless firewall issues exist, this setting probably does not need to be changed from its
default value. Default 6785.
PakBusRoutes
String
Y
•
Settings Editor:
Advanced | Route Filters
•
Status
table field: ≈45
Lists routes or router neighbors known to the CR6 at the time the setting was read. Each
route is represented by four components separated by commas and enclosed in parentheses:
(port, via neighbor adr, pakbus adr, response time).
Default =
(1, 4089, 4089, 1000)
.
Updates when routes are added or deleted.
PakBusTCP
Clients
String
•
Settings Editor:
Network Services | PakBus/TCP Clients
Up to four addresses specifying outgoing PakBus/TCP connections for the CR6 to maintain.
PakBusTCP
Enabled
Numeric
•
Settings Editor:
Datalogger | PakBus/TCP Password
Enables (
True
[default]) or disables (
False
) the PakBus TCP service.
PakBusTCP
Password
String
•
Settings Editor:
Datalogger | PakBus/TCP Password
When active (not blank), a log-in process using an MD5 digest of a random number and this
password must take place successfully before PakBus communications can proceed over an
IP socket.
PanelTemp
FLOAT
Y
•
Station Status field:
Panel Temperature
•
Status
table field: 12
Current wiring-panel temperature (°C). Measurement is made in auto self-calibration. When
auto self-calibration executes (once per minute).
PingEnabled
Numeric
•
Settings Editor:
Network Services | Ping (ICMP) Enabled
Enables (
True
[default]) or disables (
False
) the ICMP ping service.
PortConfig()
String
Y
•
Status
table field: ≈43
Sets up
C
terminals in numeric order of terminals. Set up for input, output, SDM, SDI-12,
COM port. Default =
Input
. Updates when the port configuration changes.
PortStatus()
Numeric
•
Status
table field: ≈42
States of
C
terminals configured for control. On/high (
True
) or off/low (
False
). Array
elements in numeric order of
C
terminals. Default =
False
. Updates when state changes.
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......