Section 8. Operation
449
FIGURE 99: VSPECT Vibrating Wire Measurement
Wiring
8.1.4.1.2 Static VSPECT Measurement Theory
The CR6 uses an audio
A-to-D
(p. 573)
converter to capture vibrating wire signals on
U
terminals. The graph in the figure
Unconditioned Time Domain Data
(p. 450)
shows raw time series data recorded after the vibrating wire sensor was excited
with a swept frequency. Figure
VSPECT Data
(p. 450)
shows the same data after an
FFT
(p. 583)
has been applied.
Each measurement acquires 4096 raw points. These data include all frequencies
vibrating the sensor wire. The FFT creates a frequency spectrum of these points.
The frequency spectrum shows each frequency with voltage amplitude. The
dominant frequency with the highest amplitude is the natural-resonant frequency.
Noise frequencies may be sourced from harmonics of the natural frequency,
electronic noise, or harmonics of the electronic noise. For example, 50 Hz or 60
Hz noise from
ac mains grid power
(p. 590),
and associated harmonics, are common
noise sources. Noise frequencies may also originate from mechanical obstruction
of the taut wire, such as may be caused by a loose wire or when the wire vibration
is physically changed by sensor movement. VSPECT makes possible the
separation of the natural-resonant frequency from these other frequencies.
Note
The FFT algorithm requires time for computation. Compile or
download errors will occur if the CRBasic program does not allow two
seconds for the measurement of each sensor.
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......