Section 6. Specifications
128
CR6 Power Out Limits: 12V and SW12
Terminal
Source Limit
1
SW12-1
or
SW12-2
1660 mA @ –40 °C
1290 mA @ 0 °C
1100 mA @ 20 °C
830 mA @ 50 °C
640 mA @ 70 °C
500 mA @ 85 °C
12V
+
SW12-1
+
SW12-2
3880 mA @ –40 °C
2980 mA @ 0 °C
1800 mA @ 20 °C
1350 mA @ 70 °C
1000 mA @ 85 °C
1
Thermal fuse hold current. Overload causes voltage drop. Disconnect and let
cool to reset. Operate at limit if the application can tolerate some fluctuation.
CR6 Power Out Limits: Total System
Temperature
(°C)
Current Limit at 12 Vdc
1
(Amperes)
–40°
3.80
20°
2.50
70°
1.35
85°
1.00
1
Limited by self-resetting thermal fuse
6.8
Ground Terminals — Specifications
Signal Ground:
Six common terminals ( ) for
grounds associated with sensor
signals
Power Ground:
Four common terminals (
G
) for
grounds associated with power and
control connections
Resistive Ground:
One terminal (
RG
) for decoupling
ground on RS-485 signals; 100 ohm,
2 watt resistor to ground
Ground Lug:
Heavy gage connection to earth
ground ( ); field earth ground
should be minimum five-foot
copper-sheathed ground rod
connected with minimum 14 AWG
wire
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......