SECTION 8. PROCESSING AND PROGRAM CONTROL EXAMPLES
8-9
07:
If Flag/Port (P91)
1:
21
Do if Flag 1 is Low
2:
30
Then Do
08:
Do (P86)
1:
11
Set Flag 1 High
09:
Z=F (P30)
1:
10
F
2:
0
Exponent of 10
3:
2
Z Loc [ Down_cnt ]
10:
End (P95)
11:
End (P95)
12:
IF (X<=>F) (P89)
1:
2
X Loc [ Down_cnt ]
2:
1
=
3:
0
F
4:
30
Then Do
13:
If Flag/Port (P91)
1:
11
Do if Flag 1 is High
2:
30
Then Do
14:
Serial Out (P96)
1:
81
All Data to other FS Area
15:
Do (P86)
1:
21
Set Flag 1 Low
16:
End (P95)
17:
Else (P94)
18:
Z=X+F (P34)
1:
2
X Loc [ Down_cnt ]
2:
-1
F
3:
2
Z Loc [ Down_cnt ]
19:
End (P95)
*
A
Mode 10 Memory Allocation
01:
28
Input Locations
02:
64
Intermediate Locations
03:
84
Final Storage Area 2
INPUT LOCATIONS
1 Force_kg
2 Down_cnt
8.9 LOGARITHMIC SAMPLING USING
LOOPS
A ground water pump test requires that water
level be measured and recorded according to
the following schedule.
Output Interval
Time into Test, min
Loop #
00
to
10
10 sec.
1
10
to
30
30 sec.
2
30
to
100
1 min.
3
100
to
300
2 min.
4
300
to
1000
5 min.
5
1000 and greater 10 min.
6
This is accomplished with a series of loops
(Instruction 87), where the delay and count
parameters are used to implement the
frequency of measurement (and output) and the
duration of the that frequency. The unit of delay
is the execution interval. A delay of 1 with a 10
second execution interval and a count of 60
means the instructions in the loop, in this case
measure and output water level, are executed
every 10 seconds for 10 minutes.
The drawdown portion of the test is completed
at some time greater than 1000 minutes. To
enter the recharge phase of the test, the
operator enters the
6
A
D
Mode and
sets Flag 1 high. At the next 10 minute pass
through loop 6 the loop is exited. Program
execution returns to the top of the program
table and the measurement schedule starts
over again for the recharge test.
The sensor is a 50 PSI Druck, model 930/ti with
a calibration of 49.93 mV/10V of excitation or
4.993 mV/V. Your calibration will be different.
An excitation voltage of 1500 mV yields a
maximum signal of 7.489 mV at 50 PSI, fully
utilizing the 7.5 mV Input Range to provide the
best resolution.
The multiplier, m, is calculated to provide depth
of water in feet:
m = (50 psi/4.993 mV/V) * (2.3067 ft/psi)
m = 23.099 ft/mV/V
The offset is calculated to provide a final value
that represents the distance from the lip of the
well to the water surface. Similar to Figure
7.16-2, the offset equals the initial distance of
47.23 feet plus the initial reading of 54.77, or
102 feet.
Summary of Contents for CR23X
Page 8: ...CR23X TABLE OF CONTENTS vi This is a blank page ...
Page 12: ...CR23X MICROLOGGER OVERVIEW OV 2 1 2 3 A 4 5 6 B 7 8 9 C 0 D FIGURE OV1 1 CR23X Micrologger ...
Page 34: ...CR23X MICROLOGGER OVERVIEW OV 24 This is a blank page ...
Page 50: ...SECTION 1 FUNCTIONAL MODES 1 16 This is a blank page ...
Page 72: ...SECTION 4 EXTERNAL STORAGE PERIPHERALS 4 8 This is a blank page ...
Page 88: ...SECTION 6 9 PIN SERIAL INPUT OUTPUT 6 10 This is a blank page ...
Page 110: ...SECTION 7 MEASUREMENT PROGRAMMING EXAMPLES 7 22 This is a blank page ...
Page 134: ...SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES 8 24 This is a blank page ...
Page 164: ...SECTION 9 INPUT OUTPUT INSTRUCTIONS 9 30 This is a blankpage ...
Page 188: ...SECTION 11 OUTPUT PROCESSING INSTRUCTIONS 11 8 This is a blankp age ...
Page 221: ...SECTION 13 CR23X MEASUREMENTS 13 21 FIGURE 13 5 1 Circuits Used with Instructions 4 9 ...
Page 229: ...14 3 1 2 3 A 4 5 6 B 7 8 9 C 0 D FIGURE 14 3 1 CR23X Battery Pack and Panel ...
Page 240: ...SECTION 14 INSTALLATION AND MAINTENANCE 14 14 This is a blank page ...
Page 244: ...APPENDIX A GLOSSARY A 4 This is a blank page ...
Page 268: ...APPENDIX B CONTROL PORT SERIAL I O INSTRUCTION 15 B 24 This is a blank page ...
Page 276: ...APPENDIX C BINARY TELECOMMUNICATIONS C 8 This is a blank page ...
Page 278: ...This is a blank page ...
Page 282: ...APPENDIX F DYNAGAGE SAP FLOW P67 F 4 This is a blank page ...
Page 299: ...APPENDIX I TD OPERATING SYSTEM ADDENDUM FOR CR510 CR10X AND CR23X MANUALS ...
Page 300: ...This is a blank page ...
Page 302: ...This is a blank page ...
Page 308: ...TABLE DATA ADDENDUM AD 6 This is a blank page ...
Page 324: ...TD ADDENDUM SECTION 1 FUNCTIONAL MODES AD 1 8 This is a blank page ...
Page 340: ...TD ADDENDUM SECTION 8 PROCESSING AND PROGRAM CONTROL EXAMPLES AD 8 10 This is a blank page ...
Page 342: ...This is a blank page ...
Page 373: ...This is a blank page ...