(right axis). The reading has settled to 99.5% of the final value by the fourteenth measurement,
which is contained in variable
PT(14)
. This is suitable accuracy for the application, so a settling
time of 1400 µs is determined to be adequate.
6.1.3.7
Factors
affecting
accuracy
Accuracy
describes
the
difference
between
a
measurement
and
the
true
value.
Many
factors
affect
accuracy.
This
topic
discusses
the
effect
percent-of-reading,
offset,
and
resolution
have
on
the
accuracy
of
an
analog
ue
voltage
measurement.
Accuracy
is
defined
as
follows:
accuracy
=
percent-of-reading
+
offset
NOTE:
Error discussed in this section and error-related specifications of the datalogger do not
include error introduced by the sensor, or by the transmission of the sensor signal to the
datalogger.
6. Measurements
56