The
PUMP_SETPT
check is performed continuously and
pump_flow_OK
is
set accordingly. If a CPEC300 system is in EC mode and
pump_flow_OK
is
false
, bit 6 of
diag_cpec
will be set to indicate there is a problem with the
pump flow. If a CPEC300 system is not in EC mode,
pump_flow_OK
is
ignored. See notes on bit 6.
pump_tmpr_OK
Boolean variable
pump_tmpr_OK
=
True
if the pump is within its range (0 to
55 °C) and is set to
False
if it is outside this range.
This check is performed continuously, and
pump_tmpr_OK
is set
accordingly. If a CPEC300 system is in EC mode, bit 5 of
diag_cpec
will be
set if
pump_tmpr_OK
=
False
to indicate there is a problem with the pump
temperature. If a CPEC300 system is not in EC mode,
pump_tmpr_OK
is
ignored. See notes on bit 5.
buff_depth_OK
Boolean variable
buff_depth_OK
is equivalent to bit 4 of
diag_cpec
. If the
datalogger processing falls too far behind,
buff_depth_OK
=
False
and bit 4 of
diag_cpec
will be set. See notes on bit 4.
valve_flow_OK
Boolean variable
valve_flow_OK
is defined only if the CPEC program is
configured to use a valve module. See Section
(p. 20)
, for
details.
If the valve (zero/span) flow (
valve_flow)
is within its normal range,
valve_flow_OK
=
True
but =
False
if it is outside this range. This check is
performed only if a valve is selected (
valve_number
>
0
).
The variable
valve_flow_OK
is ignored in EC mode, but if a CPEC300 system
is not in EC mode, bit 3 of
diag_cpec
will be set if
valve_flow_OK
=
False
to
indicate there is a problem with the valve flow. See notes on bit 3.
valve_tmpr_OK
Boolean variable
valve_tmpr_OK
is defined only if the CPEC program is
configured to use a valve module. See Section
(p. 20)
, for
details.
If the valve module temperature
valve_tmpr
is within its operating range (0 to
60 °C),
valve_tmpr_OK
=
True
but will =
False
if it is outside this range.
This check is performed continuously, and Boolean variable
valve_tmprOK
is
set accordingly.
The variable
valve_tmpr_OK
is ignored in EC mode, but if a CPEC300
system is not in EC mode, bit 2 of
diag_cpec
will be set if
valve_tmpr_OK
=
False, i
ndicating there is a problem with the temperature of the valve module.
See notes on bit 2.
scrub_tmpr_OK
Boolean variable
scrub_tmpr_OK
is defined only if the CPEC program is
configured to use a scrub module. See Appendix
(p. K-1)
, for details.