Operating Instructions

Programmable
isolating amplifier
SINEAX TV 809

TV 809 Be       147 802

  08.04

Camille Bauer Ltd
Aargauerstrasse 7
CH-5610 Wohlen/Switzerland
Phone +41 56 618 21 11
Fax +41 56 618 24 58
e-mail: [email protected]
http://www.camillebauer.com

The following symbols in the
Operating Instructions indicate safety
precautions which must be strictly
observed:

2. Scope of supply 

(Fig. 1 and 2)

Isolating amplifier, 

one of the two versions (1)

Order Code: Significance of the 1st to 7th digits

809 – x x x

3

Housing with screw terminals,
not pluggable

9

Housing with screw terminals, pluggable

1

Standard / Power supply 24 …   60 V DC, AC

2

Standard / Power supply 85 … 230 V DC, AC

3

[EEx ia] IIC / Power supply 24 …   60 V DC, AC

4

[EEx ia] IIC / Power supply 85 … 110 V DC / 230 V AC

1

Input current max. final value 100 mA (Standard)

2

Input current max. final value 1.5 mA

Contents

  1. Read first and then … ................................................................... 1
  2. Scope of supply ............................................................................ 1
  3. Brief description ............................................................................ 1
  4. Overview of the parts .................................................................... 2
  5. Technical data ............................................................................... 2
  6. Mounting ....................................................................................... 2
  7. Electrical connections ................................................................... 2
  8. Configuring the isolating amplifier ................................................ 3
  9. Accessories and spare parts ........................................................ 4
10. Commissioning ............................................................................. 4
11. Maintenance ................................................................................. 4
12. Releasing the isolating amplifier ................................................... 4
13. Dimensional drawings ................................................................... 4

1. Read first and then …

The proper and safe operation of the device assumes
that the Operating Instructions are 

read 

and the safety

warnings given in the various Sections

  6. Mounting

  7. Electrical connections

  8. Configuring the isolating amplifier

10. Commissioning

are 

observed.

The device should only be handled by appropriately
trained personnel who are familiar with it and authorised
to work in electrical installations.

Unauthorized repair or alteration of the unit invalidates
the warranty.

Fig. 1

1

 Operating Instructions 

(2) each in German, French and English

Ex approval

 (3), only for Ex version devices

3. Brief description

The purpose of the isolating amplifier 

SINEAX TV 809

 is to electrically

insulate input and output signals, respectively to amplify and/or change
the signal level or type (current or voltage) of the input signals.

An explosion-proof “intrinsically safe” [EEx ia] IIC version rounds off this
series of SINEAX TV 809.

Measured variables and measuring ranges are programmed with the aid
of a PC, a programming cable and the programming software. Specific
measured variable data such as output signal, transmission characteristics
and various functions in combination with the alarm function can also be
programmed.

Isolating amplifier supplied as standard versions are configured as
follows:

– Measuring input:

4 … 20 mA

– Measuring output:

4 … 20 mA

– Response time:

80 ms

– Mains ripple suppression:

For frequency 50 Hz

(1)

809 – x x x x x

(2)

0

Without alarm function

1

With built-in alarm relay

0 Without test records

D With test records in German

E With test records in English

13. Dimensional drawings

Fig. 8. SINEAX TV 809 in carrying rail housing 

P12/17

 clipped onto a top-hat rail

(35 

×

 15 mm or 35 

×

 7.5 mm, acc. to EN 50 022), 

screw terminals not pluggable.

63

69.2

17.5

114

Fig. 9. SINEAX TV 809 in carrying rail housing 

P12/17 St

 clipped onto a top-hat rail

(35 

×

 15 mm or 35 

×

 7.5 mm, acc. to EN 50 022), 

screw terminals pluggable.

63

85

17.5

114

10. Commissioning

Switch on the measuring input and the power supply.

The power supply unit must be capable of supplying a
brief current surge when switching on. The isolating
amplifier presents a low impedance at the instant of
switching which requires a current I

start

 of …

… I

start

 

 160 mA for the version with a power supply range

of 24 – 60 V DC, AC

or

… I

start

 

 35 mA for the version with a power supply range

of 85 – 230 V DC, AC

11. Maintenance

No maintenance is required.

12. Releasing the isolating amplifier

Release the instrument from a top-hat rail as shown in Fig. 7.

Fig. 7

  

1. The programming connector must not be

connected when > 253 V could be applied to the
SINEAX TV 809 input circuit.

2. The SINEAX TV 809 programming connector must

only be used with the PRKAB 600 resp. 560 and its
ancillary cable.

3. The ancillary cable must first be connected to the

PRKAB 600 resp. 560 before it is connected to the
TV 809 (see arrow).

4. The programming connector is galvanically

connected to the input circuit. Therefore no metal
parts of the plug or socket may be touched.

5. The PRKAB 600 resp. 560 must not be used with

other devices.

6. After programming is complete, the programming

connection must be removed from the TV 809.

Interface

to PC
DSUB 9p F

to
SINEAX TV 809

Ancillary cable

Programming cable PRKAB 600 resp. 560

FCC

DSUB 9p F

Interface

1 meter

Programming cable PRKAB 560
(for programming the SINEAX TV 809 non-Ex

Ancillary cable SINEAX type TV 809

143 587

1.5 meter

146 557

147 779

9. Accessories and spare parts

Description

Order No.

(3)

Configuration software TV 800 

plus

for SINEAX TV 809
Windows 95 or higher
on CD, in different languages

(Download free of charge under
http://www.camillebauer.com)

In addition, the CD contains all configuration
programmes presently available for Camille
Bauer products

Operating Instructions TV 809 Bd

147 422

in German

Operating Instructions TV 809 Bf

147 795

in French

Operating Instructions TV 809 Be

147 802

in English

Fig. 2

DSUB 9p F

Interface

1 meter

Programming cable PRKAB 600
(for programming the SINEAX TV 809 Ex

147 787