PM 1001606 000 07
Device handbook CENTRAX CU3000-CU5000
26/106
Driving a relay
Rated current
50 mA (60 mA max.)
Switching frequency (S0)
≤ 20 Hz
Leakage current
0,01 mA
Voltage drop
< 3 V
Load capacity
400 Ω … 1 MΩ
5.9 Analog outputs
Analog outputs are available for devices with corresponding I/O extensions only. See nameplate. Analog
outputs may be remote controlled.
CU3000
CU5000
Connection to an analog input card of a PLC or a control system
The device is an isolated measurement device. The individual outputs are galvanically connected, but the
modules are isolated from each other. To reduce the influence of disturbances shielded a twisted-pair
cables should be used. The shield should be connected to earth on both opposite ends. If there are
potential differences between the ends of the cable the shield should be earthed on one side only to
prevent from equalizing currents.
Under all circumstances consider as well appropriate remarks in the instruction manual of the system to
connect.