46/66
B5 Alarms
Via the logic module of the SINEAX CAM complex
contexts may be monitored. Out of them alarms can
be generated, which are shown on the graphic display
and can be acknowledged via the keys.
alarm reporting
The occurrence of an alarm is reported by a blinking
bell symbol in the upper left corner of the display, no
matter which display page is active at the moment.
The information which alarm is really active can be
found via the alarm display.
alarm display
Via the menu item alarms of the main menu one may
proceed to the alarm list. There the states of all
monitored alarms are displayed, no matter if they are
active or not.
alarm states
The alarm display gives the information if a specific
monitored alarm is active or not. The alarm number
refers to the appropriate logic function. The status
shows if the alarm is active, active acknowledged or
inactive.
acknowledgement of alarms
By pressing the key
for al longer time (>1s) the
displayed alarm will be acknowledged. It changes its
status to active acknowledged. If the alarm symbol in
the upper left corner changes accordingly, then there
is no further alarm in the alarm state.
The option
Lists
offers the possibility to record the
occurrence, the acknowledgement and the setting of
alarms with time reference in chronological and
correct order.
If the security system has been activated, also the
user who has acknowledged an alarm will be
recorded.