Mounting Options
The Scanner 2000 microEFM can be mounted using the following methods:
• Direct-mount to an orifice or cone type DP meter. The integral multi-variable sensor may be connected
to the pressure taps with stabilizers
or a heavy wall nipple with adapter flanges,
and a 5-valve manifold
). A bottom-port MVT is recommended for gas measurement; a side-mount MVT is
recommended for liquid or steam measurement.
• Direct-mount to a turbine meter. The CSA-certified instrument can be mounted to a turbine meter using a
pipe adapter and union connection (
). The ATEX-certified instrument can be mounted to
a Barton 7000 Series meter using a turbine meter pickup extension (
).
• Pole-mount. The instrument can be mounted on a 2-in. pole using a NuFlo hardware kit, or bulkhead-
mounted to a flat, vertical surface (
). Pole mounting may be preferred where limited
space or pipe vibration prohibits direct-mount installation. A horizontal pipe mount is recommended for
liquid and steam installations using a side-port MVT and block manifold. Tubing is used to connect the
integral MVT to the orifice meter or cone meter. If a Scanner 2000 will be used for steam measurement, a
condensate pot must also be installed to protect the Scanner 2000 from extreme temperatures. See
suring Steam via a Differential Pressure Meter, page
, for details.
The following accessories are also recommended:
•
a 5-valve manifold for connecting process lines to the integral MVT
• an RTD assembly for process temperature input on gas flow runs and compensated liquid flow runs (not
recommended for steam flow runs). See
Hazardous Area Installations, page 27
options to meet specific hazardous area requirements.
•
tubing and/or pipe for plumbing process connections
• explosion-proof signal cable for remote turbine connections (stranded, shielded cable is recommended)
•
terminal housing for expanding the number of inputs/outputs that can be connected to the Scanner 2000
Pole-Mount Installation
To mount the Scanner 2000 using the optional pole-mount kit, perform the following steps:
1. Determine the pipe orientation (horizontal or vertical) that will best accommodate process connections
and field wiring connections. A horizontal pipe mount is recommended for liquid and steam installations
using a side-port MVT and block manifold.
2. Connect the mounting bracket to the Scanner 2000 using the two bolts provided (
).
3. Position the U-bolt around the pipe and through the support bracket provided with the U-bolt.
4. Align the mounting bracket against the pole so that the U-bolt passes through the mounting holes in the
bracket. Place the mounting plate over the threaded ends of the U-bolt and against the bracket, and secure
the U-bolt with the two nuts provided.
5. Install and connect process piping between the Scanner 2000 and the turbine meter with appropriate fit
-
tings. Process piping installation procedures vary with each application.