Chapter 4: Startup and Configuration
55
WARNING
Chapter
4
: Startup and Configuration
Startup Procedure
WARNING – EXPLOSION HAZARD
ENSURE THAT THE AREA IS NON-HAZARDOUS BEFORE CONNECTING A PC TO A
SERIAL PORT, OPENING THE ENCLOSURE OR ADDING OR REMOVING ANY WIRES.
1.
Ensure that the “Backup Batt” jumper (CN20) is positioned across the “ON” or upper pins. See
, for details.
2.
Ensure that the “RAM Size” Jumper (CN10) is positioned in the desired location. “High” is 96
kbytes, “Low” is 64 kbytes. See
, for details.
3.
Ensure that power is connected to terminals 2 (+) and 3 (-) on the main circuit board.
4.
If a battery is used, ensure that it is connected to terminals 4 (+) and 5 (-).
5.
Turn the power switch (SW9) on.
6.
Ensure that the correct firmware version is installed in the Scanner. The firmware version can be
viewed from the ScanWin user interface or by turning on the
Power
switch (SW9) and watching
the local display until it scrolls to the firmware version. The typical firmware version will be
NFLo or IGas X4.3.4G or higher, where X identifies firmware options such as M for Modubs or
P for ScanPLC. If the firmware needs to be updated, follow the procedure in Appendix D,
Flashing the Scanner
.
7.
Perform a superboot (see the procedure below) and continue to set up the Scanner using the setup
steps on page
.
Superbooting the Scanner
After power has been applied to the Scanner for the first time, a superboot is recommended for
initializing the memory.
Note
: If the Scanner has been
FLASHED
with the desired version of firmware or is
NOT
CONFIGURED
, perform a
superboot
. If it is already configured, it is not necessary to
perform a superboot. If a previous configuration was saved, the configuration can be restored
after a superboot is performed.
Note
: Superbooting
ERASES
all configuration and history data.
SAVE
all configuration and history
data before superbooting the Scanner RTU. See the ScanWin manual for instructions on
saving configuration data.
Summary of Contents for NUFLO 1141C
Page 1: ...Manual No 30165009 Rev 01 NUFLOTM Scanner 1141 RTU Hardware User Manual ...
Page 28: ...Scanner 1141 Hardware User Manual 28 Figure 3 1 Scanner 1141 main circuit board ...
Page 66: ...Scanner 1141 Hardware User Manual 66 ...
Page 67: ...Chapter 6 Parts List and Order Code 67 Chapter 6 Parts List and Order Code Scanner 1141C ...
Page 68: ...Scanner 1141 Hardware User Manual 68 Scanner 1141L ...
Page 69: ...Chapter 6 Parts List and Order Code 69 Scanner 1141G ...
Page 91: ...Appendix A Specifications 91 Outline Dimensions Scanner 1141C ...
Page 92: ...Scanner 1141 Hardware User Manual 92 Scanner 1141L Front and Side Views ...
Page 94: ...Scanner 1141 Hardware User Manual 94 Scanner 1141G ...
Page 96: ...Scanner 1141 Hardware User Manual 96 Drawing 1 Installation ...
Page 97: ...Appendix B Control Drawings 97 Drawing 2 Power Supply ...
Page 98: ...Scanner 1141 Hardware User Manual 98 Drawing 3 Communications Serial Ports ...
Page 99: ...Appendix B Control Drawings 99 Drawing 4 Status Pulse Inputs Outputs ...
Page 100: ...Scanner 1141 Hardware User Manual 100 Drawing 5 RTD Inputs Analog Inputs Outputs ...
Page 101: ...Appendix B Control Drawings 101 Drawing 6 Analog Outputs ...
Page 102: ...Scanner 1141 Hardware User Manual 102 ...
Page 117: ...117 ...
Page 118: ...118 ...
Page 119: ......
Page 120: ......