Heat dissipation specifications
7.1
Description of the heat dissipation environment
The working environment of MLU-X1000 is as follows:
1Table 7.1 Working environment of MLU-X1000
Items
Specification parameters
Working environment temperature
0~35
℃
Relative humidity
20%~85% no condensation
Noise
62~88 dBA
Note: There will be 62~88dbA noise during normal operation. Please take adequate sound insulation
measures in advance.
MLU-X1000 air volume description:
MLU-X1000 can provide up to 360 CFM of air volume
Do not block the front and rear ventilation areas of the chassis during operation of MLU-X1000
When installing MLU-X1000, please reduce the air resistance around the inlet and outlet of the
chassis
Please follow the instructions to arrange the cable to minimize the air resistance of the air flue
Please install the chassis cover before using MLU-X1000. If CXM1000 is used without the chassis
cover, the components may be damaged.
If you need to replace the fan, please make sure to complete within 25s to avoid overheating of
the system.