Chapter 12: Alarm Management and Troubleshooting
Configuring External Alarms
phn-3965_006v002
Page 12-13
Figure 402: Voltage Alarm Configuration Page
2
To mask the undervoltage alarm, select
Enable
in the appropriate row in the Alarm Parameters section of
the Alarm Configuration page, then click
Apply
:
•
Mask undervoltage alarm on 1st DC power feed
–
Select
Enable
to mask the undervoltage alarm for the
power feed on the left.
•
Mask undervoltage alarm on 2nd DC power feed
–
Select
Enable
to mask the undervoltage alarm for the
power feed on the right.
3
To change the undervoltage and overvoltage alarm thresholds, click
Edit
. The Voltage Alarm Configuration
–
Edit page opens.
Figure 403: Voltage Alarm Configuration
–
Edit Page
4
Select the thresholds you want in the
Undervoltage clear threshold (V)
,
Undervoltage raise threshold (V)
,
Overvoltage clear threshold (V)
, and
Overvoltage raise threshold (V)
fields. The configurable values for these
thresholds are 0-100V.
5
Click
Apply
.