AFX SERIES® OPERATION MANUAL
SECTION 5: UNPACKING AND INSTALLATION
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS)
• All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 88 of 402
5.19.2
System Grounding
1.
All AFX Cabinet systems MUST be properly grounded to the local facility ground
using the provided GROUND terminal on the AC input terminal block located inside
the cabinet.
2.
In addition to individual facility ground connections, Multi-Cabinet units must be
grounded to each other. This may be accomplished by connecting a ground cable to
the rear of the cabinet rack on the designated Master Cabinet, passing the cable
through the Input / Output power strain reliefs, and terminating the cable on the
rear of the cabinet rack of the designated Auxiliary cabinet.
Refer to diagram above for suggested ground wire routing between two cabinets.
NOTE: Each cabinet should still be ground to facility ground.