5.18.2
Parallel System Bus Connection
For both units to operate correctly, the system bus connections between the master and
auxiliary units MUST be made. This is done by daisy chaining the master to the first auxiliary
and that auxiliary to the next one.
The system interface connectors are located on the left hand side of the rear panel and
marked as follows:
PARALLEL IN
On the MASTER unit, this connector is NOT CONNECTED. This causes the
unit to become a master for other parallel units at power on. On an AUX
unit, this connector is connected to a MASTER unit or an AUX unit that
precedes this unit in the parallel chain.,
PARALLEL OUT
On the MASTER unit, this connector is connected to the first AUX unit. On
the last AUX unit in the parallel chain, this connector is NOT CONNECTED
signifying the end of the parallel chain.
The system bus uses a DVI-I Dual Link Male to Male interconnect cable with noise
suppression ferrite beads. Cable length for paralleling units that are stacked in a 19” cabinet
with no more than 1U space between units is 1 foot (0.3 m). Use of longer cables than 1
foot /30 cm is not recommended. If units cannot be installed in a cabinet, a longer DVI cable
up to 3 feet in length may be used as an exception.
An example of the interconnect between one MASTER and one AUX is shown in the figure
below.
Note: Any unused Parallel bus connector must be covered by the included safety covers.