FLOW METER INSTALLATION
m aking
since 1986
water work
FLOW METER
INSTALLATION
Page 1: ...FLOW METER INSTALLATION making since 1986 water work FLOW METER INSTALLATION...
Page 2: ...ated further around the pipe from the top but not more than 45 degrees from top dead center The sensor should never be located at the bottom of the pipe as sediment may collect there Locations off top...
Page 3: ...and one 1 RED standard 14 AWG irrigation wire The Flow Meter has two wire leads one 1 BLACK and one 1 RED At the controller the BLACK wire in the BLACK harness is connected to the BLACK Flow Meter wi...
Page 4: ...pe diameter downstream of the flow meter provide no flow disturbances There should be no pipe bends fittings or valves within these minimum distances The insertion depth and alignment of the sensor as...
Page 5: ...provided or some other acceptable lubricant Note Take care not to get any grease on the impellor or bearing Insert the Flow Sensor into the 2 NPT adapter so that the mounting holes in the positioning...
Page 6: ...impeller into the fluid flow As a backup to the flow label there is a small hole next to the larger sighting hole of the upstream side With a 3 32 Allen wrench tighten positioning collar screws Double...
Page 7: ...FLOW METER INSTALLATION making since 1986 water work FLOW METER TRANSIENT PROTECTION FOR LIGHTNING PRONE AREAS...