Maintain external cable connections
Check external cable connections at least once a year. External cable is defined as any cable
or wire that enters the cabinet from an external source.
•
Visually inspect all cables for signs of physical damage. If damage is present cables
should be repaired or replaced, if possible, per local site practices.
•
Check all outside plant copper connections for complete and secure connection.
•
Ensure that all cable management accessories provide a clean appearance. Replace
any fastening devices (i.e. tie wraps) so that they include all cables being secured.
•
Check all fiber optic connectors to ensure that they are securely fastened.
•
Check all connections on the cabinet ground bar for a tight and secure fit.
•
Check all protector modules and fiber modules to ensure that all devices are
securely seated.
•
Check all conduits to ensure that any material used to seal between the cable and
the conduit is still present and providing a complete seal.
Summary of Contents for ODC-10
Page 1: ...Calix ODC 80 Installation Guide July 2003 Part 220 00029 Rev 11...
Page 2: ......
Page 6: ......
Page 7: ...1 Chapter Before You Begin Installing the ODC 80...
Page 8: ......
Page 23: ...2 Chapter Placing the ODC 80 on a Pad...
Page 24: ......
Page 30: ......
Page 31: ...3 Chapter Installing Power Subscriber Cables and Equipment...
Page 32: ......
Page 74: ......
Page 75: ...4 Chapter Maintaining and Troubleshooting the ODC 80...
Page 76: ......
Page 80: ......
Page 92: ......
Page 103: ...5 Chapter Reference...
Page 104: ......
Page 106: ......