7. Service
7.1 Cleaning
The exterior of the power source may be cleaned with a cloth dampened with a mild detergent
or
7.2 G
and wrung out. Disconnect mains power to the source before cleaning. Do not spray water
other cleaning agents directly on the power source.
eneral
This section describes the suggested maintenance and troubleshooting procedures. The
7.3 B
troubleshooting procedure is divided into two sections. The first section deals with basic
operation and connection of the equipment. The second section requires opening the unit and
using LED indicators and a simple multimeter to troubleshoot the unit down to the module level.
Only a qualified electronic technician should attempt this level troubleshooting.
asic operation
PARAGRAPH
PROBLEM
Excessive Output Voltage
Poor Output Voltage Regulation
Overload Light On
Output
Unit Shuts Down After 1-2 Seconds
No Output and no lights on front panel
No output, but front panel controller is active.
Table 7-1: Basic Symptoms
7.3.1 Excessive Output Voltage
CAUSE
SOLUTION
External sense not connected (If used)
Connect external sense wires from TB2 on
rear panel to the AC power outlet TB1A
and TB1B
7.3.2 Poor Output Voltage Regulation
CAUSE
SOLUTION
Unit is overloaded
Remove overload
Unit is programmed to wrong voltage
range.
Select correct voltage range.
Input line has fallen below spec. limit.
Check input supply voltage.
MX
Series