User Manual – Rev AJ
California Instruments
3. Unpacking and Installation
3.1 Unpacking
Inspect the unit for any possible shipping damage immediately upon receipt. If damage is
vident, notify the carrier.
DO NOT
return an instrument to the factory without prior approval.
Do not destroy the packing container until the unit has been inspected for damage in shipment.
ed
e
If possible,
retain the container
(wooden crate) in the event the system ever has to be return
to the factory for either repair or upgrades
WARNING: This power source weighs approximately 1150 lbs / 522
Kg
. Obtain
adequate help when moving the unit. Make sure the location (floor) in which the MX
Series unit(s) will be installed can support the weight of the unit(s).
3.2 Power Requirements
The MX Series power Source has been designed to operate from a three-phase, three wire
(Wye or Delta) AC input line. A protective earth connection is required as well. (PE).
Available three-phase input settings are 208 V
LL
(option -208), 230 V
LL
(option -230), 400 V
LL
(option -400), or 480 V
LL
(option -480).
Figure 3-1: The MX45 Power Source
CAU
30V unit, the result
TION: Do not connect 400 or 480V into a unit set for 208 or 2
could be a severely damaged unit. Always check the input rating on the model
number tag before connecting AC input power. Consult factory if input settings have
to be changed.
36 MX
Series