Function

Float type automatic air vent designed to vent air that is released
from  the  water  at high points in piping.  Example 
applications include domestic hot water storage tanks and 
recirculation system pump inlets. Compatible with plumbing 
systems low-lead brass body certified and listed by ICC-ES. 

Product range

Code NA502640A         Low-lead automatic air vent ½” NPT male

Technical characteristics

Materials:  Body: 

           DZR low-lead brass

Seals: 

                                               peroxide-cured EPDM 

  
Performance:  Max. working pressure: 

150 psi (10 bar)

 

Max. discharge pressure: 

90 psi (6 bar)

 

Max. discharge flow rate: 

1.75 scfm (0.83 l/s)

 Max. 

working temperature: 

240°F (115°C)

 
NSF/ANSI 372-2011, Drinking Water System Components-Lead Content 
Reduction of Lead in Drinking Water Act, California Health and Safety Code 
116875 S.3874, Reduction in Drinking Water Act, certified by ICC-ES, file PMG-1360.

PLUMBVENT™ Low-lead automatic air vent

                             

                                         

NA502640A

© Copyright 2018 Caleffi

H0004951

www.caleffi.com

Installation

The vent is installed in the vertical position on riser pipes and generally in parts of the system 
where a concentration of air pockets is to be expected.

Operating instructions

The automatic air vent can be used for manual or automatic venting of hydronic and plumbing 
systems. The automatic air vent is supplied complete with a safety hygroscopic cap that 
automatically closes the air discharge in case of contact with water.

For normal automatic venting, keep hygroscopic cap closed for a slow release of air. A fast release 
of the air may allow dirt or scale in the water to plug the operating mechanism. The small hole in 
the side of the cap allows air to escape.

Service instructions

For optimum performance replace hygroscopic cap every 3 years. The natural cellulose fiber 
washers can deteriorate over time when exposed to unfiltered or hard water.

1

Summary of Contents for PLUMBVENT NA502640A

Page 1: ...Act certified by ICC ES file PMG 1360 PLUMBVENT Low lead automatic air vent NA502640A Copyright 2018 Caleffi H0004951 www caleffi com Installation The vent is installed in the vertical position on riser pipes and generally in parts of the system where a concentration of air pockets is to be expected Operating instructions The automatic air vent can be used for manual or automatic venting of hydron...

Page 2: ...ll not be liable for damages resulting from stress corrosion misapplication or misuse of it products CAUTION Make sure that all the connecting pipework is water tight CAUTION If the air vent is not installed commissioned and maintained properly according to the instructions contained in this manual it may not operate correctly and may endanger the user 2 CAUTION Uncontrolled venting of water can o...

Page 3: ...ON Si le Purgeur d air automatique n est pas installé mis en service et entretenu correctement selon les instructions contenues dans ce manuel il peut ne pas fonctionner correctement et peut mettre en danger l utilisateur ATTENTION S assurer que tous les raccordements sont étanches Caleffi ne pourra être tenue responsable des dommages résultant de la corrosion d une mauvaise utilisation ou une mau...

Page 4: ...83 West Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 3 30 18 LEAVE THIS MANUAL WITH THE USER Laissez ce manuel à la disposition de l utilisateur 4 DCW or DHW circulator Typical application diagrams WATER HEATER ...

Reviews: