background image

Function

The FlowCal™ automatic flow balancing valve maintains a

constant fixed flow rate within varying system differential

pressure ranges. Operation is fully automatic requiring no

manual adjustment. The 121 series utilize an exclusive,

interchangeable flow cartridge, made of anti-scale, low

noise polymer for use in cooling and heating systems. The

FlowCal 121 series automatic flow balancing valves are

available with integral shut-off ball valve and optional

factory-installed pressure and temperature test ports.

Drain valves are also available as an accessory for

installing in the blowdown port connection.

Product range

121 Series Automatic flow balancing valve with polymer cartridge, ball valve, with and without

Pressure and Temperature Test ports;

sizes 1/2" - 3/4" - 1" - 1 1/4"

Technical characteristics

Material:

Body:

FlowCal flow cartridge:

Spring:

Seals:

Ball:

Ball seat and stem seal:

Lever:

Pressure and temperature test port plugs:

Pressure and temperature test ports:

Drain port plug:

brass

anti-scale

 

polymer

stainless

 

steel

peroxide-cured 

EPDM

brass,

 

chrome-plated

PTFE

zinc

 

coated

 

steel

 

with

 

vinyl

 

grip

 

brass

body

 

and

 

cap-

 

brass;

 

core-

 

nordel

 

brass

Performance:

Medium:

water, glycol solutions

Max. percentage of glycol:

50%

Max. working pressure:

400 psi (400 WOG)

Working temperature range:

32-212°F (0-100°C)

Connections:

1/2", 3/4", 1", 1-1/4" FNPT or Sweat with union x FNPT or Sweat

Pressure and temperature test ports connections:

1/4" FNPT

Blowdown port connection:

1/2" - 3/4": 1/4" FNPT

1" - 1 1/4": 1/2" FNPT

Flow rate:

27 flow rate settings ranging from 0.5 - 21 GPM

Flow accuracy:

±10%

Differential Pressure Control Ranges:

2-14, 2-32, 4-34, 5-35, 3-32, 4-35

Identification:

metal plate with ball chain stating

P range and fixed flow rate

CALEFFI

FlowCal™ Automatic flow balancing valve with polymer cartridge

121 Series

NA18055

.0

2

www.caleffi.com

©

 

Copyright

 

201

Caleffi

These items are designed for use in closed hydronic systems. Do not use in 

plumbing applications. These items do not meet the low-lead plumbing standards of 

U.S. and Canada.