background image

5

Problem

1

Temperature 1 above maximum value set for drain

2

Temperature below minimum value, risk of frost

3

Pressure above maximum absolute level

4

Temperature above maximum absolute level

5

Discharge air vent blocking condition

6

Filling not completed error

7

Incorrect offset detected

8

Error: no power supply

Drain temperature limitation

The system has a function to reduce the temperature of drainage water. During the cleaning cycle, if the system detects that the medium temperature 
is higher than the set temperature, the system operates relay G.OUT, which remains energized until the drainage cycle ends. Energization of relay G. 
OUT must be employed by the user as a method of reducing the drain water temperature of the device, for example through a valve that injects cold 
water into the drain. Check the local regulations in force.

Faults

Abnormal operating conditions do not cause the device to stop operating but are shown on the display, making it possible to prevent possible more 
serious problems (red LED flashing on the front panel). Faults are also recorded in a specific memory zone accessible via Modbus. The fault signal 
persists until the user performs an alarms/faults reset, operating on the user interface or via Modbus, or when the fault in question is resolved. Contact 
Caleffi technical service if you are unable to solve the problem unassisted. 

Alarm management

The alarms (or blocking alarms) show conditions that prevent correct operation of the device or conditions of danger for the system. Following 
identification of a possible hazard condition, the system assumes standby status and remains in a condition of safety to limit any possible damage or 
malfunctions of the main system. Signalling of the alarm state is provided by the user interface (red LED steady on), and via the alarms signalling relay 
(ALARM relay, closing), and via Modbus, by means of specific registers that indicate the type of alarm identified. The alarms are recorded in a suitable 
memory zone and can be read and checked via ModBus. In the case of non-resettable alarms, following the corrective action an “alarms reset” is 
required to allow the device to perform a loading cycle and assume correct operating status: during this phase, check that there are no anomalous 
operating conditions.
NOTE: On the main page the error is indicated, e.g. as E01, while in the alarms history only the identification number 01 is shown.

Identification

 number

Identifier

Cause

Corrective action

E 01

low pressure alarm on 

sensor 1

system not pressurized

(e.g. start up in “no load” condition)

bring the circuit up to pressure, 

vent the circuit and perform an alarms reset operation

sensor not inserted correctly

depressurize the system and, in conditions of safety, check the 

correct insertion of pressure sensor P1, if necessary removing 

it momentarily and then refitting it in its seat. Clear the alarm 

with an alarms reset operation.

low pressure in device

check that any shut-off valves installed upstream from the 

device are open, check the direction of flow and perform an 

alarms reset

E 02

low pressure alarm on 

sensor 2

system not pressurized

pressurize the system 

and perform an alarms reset.

sensor not inserted correctly

depressurize the system and, in conditions of safety, check the 

correct insertion of pressure sensor P1, if necessary removing 

it momentarily and then refitting it in its seat. Clear the alarm 

with an alarms reset operation.

E 03

leak alarm

additives filling cap not screwed on 

correctly

check and restore the seal of the additives filling cap. Perform 

an alarms reset

seepage from air vent valve

Temporarily close the air vent valve cap and isolate and empty 

the device and then replace the dirty air vent valve. Perform an 

alarms reset.

seepage from drain ball valve

disconnect the electric supply, isolate and empty the device 

and replace the drain ball valve. Reconnect the electric supply 

and perform a device reset.

 generic seepage

check all the seals and tighten wherever possible 

or restore the seal

E 04

seepage alarm

inlet valve for domestic water 

washing dirty and seeping.

Close the inlet valve and empty the device. Disconnect the 

electric supply and close the shut-off valve upstream from the 

domestic water inlet. Replace the domestic water shut-off 

solenoid valve. Restore operation of the device and perform an 

alarms reset

6

Summary of Contents for DIRTMAGCLEAN 579 Series

Page 1: ...nel Display Operating principle Menu Forcing menu Parameters menu Historic data menu Communication Information Drainage temperature limitation Faults Alarm management 2 3 4 6 7 11 PROGRAMMING MANUAL C...

Page 2: ...ay The following information normally appears on the display Day of the week Probe S1 pressure Operating status Measured p Time Probe S1 temperature B battery alarm I input relay IN1 energized Operati...

Page 3: ...phase you can supply the necessary additives to the device 1 5 Automatic checks Use the UP or DOWN keys to select the submenu The regulator performs a periodic check on operation of the various strain...

Page 4: ...selected based on the plant characteristics values lower than 10kPa cannot be selected Delayed Dp When Dp exceeds a specified value the same value used to start the instantaneous cleaning cycle cleani...

Page 5: ...the alarm error code DATE and TIME show the exact moment when the alarm tripped 3 2 Faults Press OK to view the faults history The fault number is displayed with the associated code date and time of r...

Page 6: ...llowing the corrective action an alarms reset is required to allow the device to perform a loading cycle and assume correct operating status during this phase check that there are no anomalous operati...

Page 7: ...e network to have the actuator replaced isolate and empty the device disconnect the electric supply replace the motor and return the system to operation Perform the alarms reset fuses fault disconnect...

Page 8: ...his the plant must be de energised and the device must be emptied Once the new sensor has been installed proceed with the alarm reset E 23 sensor 1 temperature measurement error sensor internal fault...

Page 9: ...ARM 1 2 3 4 5 6 This connection can be made using a shielded twisted pair with minimum conductor size of 0 5 mm2 Maximum length of connections between one device and another is 2 95 m The cable must b...

Page 10: ...A ADDRESS Function 0x06 Write Single Register Used to write a single parameter 16 bit The frame has the following structure dev Addr Address of the device on the RS485 net 1 250 Func Function code 6 R...

Page 11: ...alve blocked closed alarm bit 8 measurement error alarm on sensor 1 alarm with automatic alarm reset bit 9 sensor 1 not correctly connected alarm with automatic alarm reset bit 10 measurement error al...

Page 12: ...ak alarm 16 sensor 2 clip break alarm 20 sensor 1 pressure measurement error 21 sensor 1 pressure measurement over range error 22 sensor 1 pressure measurement under range error 23 sensor 1 temperatur...

Page 13: ...onth enabled for cleaning 1 28 PA0009 1009 Cleaning start minute 1 1 0 59 59 PA0010 1010 Cleaning start hour 1 1 0 23 23 PA0013 1013 Maximum pressure delta in tenths of a KPa 1 1 100 150 5000 PA0017 1...

Page 14: ...14...

Reviews: