Summary of Contents for DIRTMAGCLEAN 579 Series

Page 1: ...nel Display Operating principle Menu Forcing menu Parameters menu Historic data menu Communication Information Drainage temperature limitation Faults Alarm management 2 3 4 6 7 11 PROGRAMMING MANUAL C...

Page 2: ...ay The following information normally appears on the display Day of the week Probe S1 pressure Operating status Measured p Time Probe S1 temperature B battery alarm I input relay IN1 energized Operati...

Page 3: ...phase you can supply the necessary additives to the device 1 5 Automatic checks Use the UP or DOWN keys to select the submenu The regulator performs a periodic check on operation of the various strain...

Page 4: ...selected based on the plant characteristics values lower than 10kPa cannot be selected Delayed Dp When Dp exceeds a specified value the same value used to start the instantaneous cleaning cycle cleani...

Page 5: ...the alarm error code DATE and TIME show the exact moment when the alarm tripped 3 2 Faults Press OK to view the faults history The fault number is displayed with the associated code date and time of r...

Page 6: ...llowing the corrective action an alarms reset is required to allow the device to perform a loading cycle and assume correct operating status during this phase check that there are no anomalous operati...

Page 7: ...e network to have the actuator replaced isolate and empty the device disconnect the electric supply replace the motor and return the system to operation Perform the alarms reset fuses fault disconnect...

Page 8: ...his the plant must be de energised and the device must be emptied Once the new sensor has been installed proceed with the alarm reset E 23 sensor 1 temperature measurement error sensor internal fault...

Page 9: ...ARM 1 2 3 4 5 6 This connection can be made using a shielded twisted pair with minimum conductor size of 0 5 mm2 Maximum length of connections between one device and another is 2 95 m The cable must b...

Page 10: ...A ADDRESS Function 0x06 Write Single Register Used to write a single parameter 16 bit The frame has the following structure dev Addr Address of the device on the RS485 net 1 250 Func Function code 6 R...

Page 11: ...alve blocked closed alarm bit 8 measurement error alarm on sensor 1 alarm with automatic alarm reset bit 9 sensor 1 not correctly connected alarm with automatic alarm reset bit 10 measurement error al...

Page 12: ...ak alarm 16 sensor 2 clip break alarm 20 sensor 1 pressure measurement error 21 sensor 1 pressure measurement over range error 22 sensor 1 pressure measurement under range error 23 sensor 1 temperatur...

Page 13: ...onth enabled for cleaning 1 28 PA0009 1009 Cleaning start minute 1 1 0 59 59 PA0010 1010 Cleaning start hour 1 1 0 23 23 PA0013 1013 Maximum pressure delta in tenths of a KPa 1 1 100 150 5000 PA0017 1...