background image

13

PA0008

1008

Bit mask for days of week 

enabled for cleaning.

1

1

0x00

0x00

0x7F

Depending on the cleaning period 
setting, the register may have different 
definitions and contents.
 Daily period: register is not used be-
cause cleaning is enabled every day.
 Weekly period: register assumes 
meaning of mask of days enabled for 
cleaning.
 Meaning of the configuration register 
bits (1=enabled,0=disabled):
bit 0: Monday Enabling of disinfection
bit 1: Tuesday Enabling of disinfection
bit 2: Wednesday Enabling of disinfec-
tion
bit 3: Thursday Enabling of disinfection
bit 4: Friday Enabling of disinfection
bit 5: Saturday Enabling of disinfection
bit 6: Sunday Enabling of disinfection
bit 7: undefined

 Two-weekly period: the register as-
sumes the meaning of the number of 
the day of the two weeks enabled for 
cleaning (1-14).
 Monthly period: the register assumes 
the meaning of the date of the month 
enabled for cleaning 
 (1-28).

PA0009

1009

Cleaning start minute.

1

1

0

59

59

PA0010

1010

Cleaning start hour.

1

1

0

23

23

PA0013

1013

Maximum pressure delta in 

tenths of a KPa

1

1

100

150

5000

PA0017

1017

Number of sleep weeks

1

1

0

4

30

PA0018

1018

Maximum drain temperature in 

degrees.

1

1

30

50

80

PA0034

1034

Maximum pressure delta per 

initial cleaning cycle in tenths 

of a KPa

1

1

10

200

5000

PA0036

1036

pressure offset for sensor 1 in 

tenths of a Kpa.

1

1

-2000

0

2000

PA0037

1037

pressure offset for sensor 2 in 

tenths of a Kpa.

1

1

-2000

0

2000

PA0039

1039

duration of initial cleaning cycle 

period in hours.

1

1

24

24

480

CMD0000

2000

cleaning start command

1

1

0

1

CMD0001

2001

additives supply start com-

mand

1

1

0

1

CMD0002

2002

device sleep phase start 

command

1

1

0

1

CMD0003

2003

device sensors control enabling 

command

1

1

0

1

CMD0004

2004

initial cleaning cycle enabling 

command

1

1

0

1

CMD0010

2010

alarm and fault condition reset 

command.

1

1

0

1

CMD0011

2011

command to reset the fault 

conditions identified.

1

1

0

1

CMD0023

2023

device reset command

1

1

1

1

Summary of Contents for DIRTMAGCLEAN 579 Series

Page 1: ...nel Display Operating principle Menu Forcing menu Parameters menu Historic data menu Communication Information Drainage temperature limitation Faults Alarm management 2 3 4 6 7 11 PROGRAMMING MANUAL C...

Page 2: ...ay The following information normally appears on the display Day of the week Probe S1 pressure Operating status Measured p Time Probe S1 temperature B battery alarm I input relay IN1 energized Operati...

Page 3: ...phase you can supply the necessary additives to the device 1 5 Automatic checks Use the UP or DOWN keys to select the submenu The regulator performs a periodic check on operation of the various strain...

Page 4: ...selected based on the plant characteristics values lower than 10kPa cannot be selected Delayed Dp When Dp exceeds a specified value the same value used to start the instantaneous cleaning cycle cleani...

Page 5: ...the alarm error code DATE and TIME show the exact moment when the alarm tripped 3 2 Faults Press OK to view the faults history The fault number is displayed with the associated code date and time of r...

Page 6: ...llowing the corrective action an alarms reset is required to allow the device to perform a loading cycle and assume correct operating status during this phase check that there are no anomalous operati...

Page 7: ...e network to have the actuator replaced isolate and empty the device disconnect the electric supply replace the motor and return the system to operation Perform the alarms reset fuses fault disconnect...

Page 8: ...his the plant must be de energised and the device must be emptied Once the new sensor has been installed proceed with the alarm reset E 23 sensor 1 temperature measurement error sensor internal fault...

Page 9: ...ARM 1 2 3 4 5 6 This connection can be made using a shielded twisted pair with minimum conductor size of 0 5 mm2 Maximum length of connections between one device and another is 2 95 m The cable must b...

Page 10: ...A ADDRESS Function 0x06 Write Single Register Used to write a single parameter 16 bit The frame has the following structure dev Addr Address of the device on the RS485 net 1 250 Func Function code 6 R...

Page 11: ...alve blocked closed alarm bit 8 measurement error alarm on sensor 1 alarm with automatic alarm reset bit 9 sensor 1 not correctly connected alarm with automatic alarm reset bit 10 measurement error al...

Page 12: ...ak alarm 16 sensor 2 clip break alarm 20 sensor 1 pressure measurement error 21 sensor 1 pressure measurement over range error 22 sensor 1 pressure measurement under range error 23 sensor 1 temperatur...

Page 13: ...onth enabled for cleaning 1 28 PA0009 1009 Cleaning start minute 1 1 0 59 59 PA0010 1010 Cleaning start hour 1 1 0 23 23 PA0013 1013 Maximum pressure delta in tenths of a KPa 1 1 100 150 5000 PA0017 1...