12

MON0025

25

status of command outputs, 

represented with an 8-bit 

integer.

1

0

Bit 0: motor command 
Bit: 1 drain valve command
Bit: 2 domestic water valve command
Bit: 3 inlet valve command
Bit: 4 cooling output command
Bit: 5 inhibition output command
Bit: 6 alarm output command
Bit: 7 voltage free output command

U8

MON0027

27

status of inputs, represented 

with an 8-bit integer.

1

0

Bit: 0 inhibition input status

U8

MON0030

30

number of cleaning cycles 

performed by the device, repre-

sented with a 16-bit integer

1

0

U16

MON0031

31

alarm code present on device, 

represented with an integer

1

0

Alarm identification code:
1:  low pressure alarm on sensor 1
2: low pressing alarm on sensor 2
3: leakage alarm
4: seepage alarm
5: inlet valve blocked alarm
7: drain valve blocked open alarm
8: drain valve blocked closed alarm
10:  error, communication with sensor 1 
not possible
12: error, communication with sensor 2 
not possible
13 : domestic water low pressure alarm
14: air vent blocked alarm
15: sensor 1 clip break alarm
16: sensor 2 clip break alarm
20: sensor 1 pressure measurement 
error
21: sensor 1 pressure measurement 
over range error
22: sensor 1 pressure measurement 
under range error
23: sensor 1 temperature measurement 
error
24: sensor 1 temperature measurement 
over range error
25: sensor 1 temperature measurement 
under range error
26: sensor 2 pressure measurement 
error
27: sensor 2 pressure measurement 
over range error
28: sensor 2 pressure measurement 
under range error
29: sensor 2 temperature measurement 
error
30: sensor 2 temperature measurement 
over range error
31: sensor 2 temperature measurement 
under range error

U8 

PA0000

1000

Current day (from 1 to 31).

1

1

1

1

31

PA0001

1001

Current month (from 1 to 12).

1

1

1

1

12

PA0002

1002

Current year (from 18 to 99).

1

1

18

18

99

PA0003

1003

Current time.

1

1

0

0

23

PA0004

1004

Current minutes.

1

1

0

0

59

PA0005

1005

Device communication config-

uration bit.

1

1

0x00

0x03

0xFFFF

bit 0 : enable communication with 
MODBUS protocol
   0 = communication not enabled 
bit   1 =  communication enabled
bit 1: communication parity enabling
   0 = parity not enabled 
   1 = parity enabled
bits 2-7: undefined

PA0006

1006

Language selection

1

1

0x00

0x00

0x03

   00 = IT
   01 = EN
   02 = FR
   03 = DE

Summary of Contents for DIRTMAGCLEAN 579 Series

Page 1: ...nel Display Operating principle Menu Forcing menu Parameters menu Historic data menu Communication Information Drainage temperature limitation Faults Alarm management 2 3 4 6 7 11 PROGRAMMING MANUAL C...

Page 2: ...ay The following information normally appears on the display Day of the week Probe S1 pressure Operating status Measured p Time Probe S1 temperature B battery alarm I input relay IN1 energized Operati...

Page 3: ...phase you can supply the necessary additives to the device 1 5 Automatic checks Use the UP or DOWN keys to select the submenu The regulator performs a periodic check on operation of the various strain...

Page 4: ...selected based on the plant characteristics values lower than 10kPa cannot be selected Delayed Dp When Dp exceeds a specified value the same value used to start the instantaneous cleaning cycle cleani...

Page 5: ...the alarm error code DATE and TIME show the exact moment when the alarm tripped 3 2 Faults Press OK to view the faults history The fault number is displayed with the associated code date and time of r...

Page 6: ...llowing the corrective action an alarms reset is required to allow the device to perform a loading cycle and assume correct operating status during this phase check that there are no anomalous operati...

Page 7: ...e network to have the actuator replaced isolate and empty the device disconnect the electric supply replace the motor and return the system to operation Perform the alarms reset fuses fault disconnect...

Page 8: ...his the plant must be de energised and the device must be emptied Once the new sensor has been installed proceed with the alarm reset E 23 sensor 1 temperature measurement error sensor internal fault...

Page 9: ...ARM 1 2 3 4 5 6 This connection can be made using a shielded twisted pair with minimum conductor size of 0 5 mm2 Maximum length of connections between one device and another is 2 95 m The cable must b...

Page 10: ...A ADDRESS Function 0x06 Write Single Register Used to write a single parameter 16 bit The frame has the following structure dev Addr Address of the device on the RS485 net 1 250 Func Function code 6 R...

Page 11: ...alve blocked closed alarm bit 8 measurement error alarm on sensor 1 alarm with automatic alarm reset bit 9 sensor 1 not correctly connected alarm with automatic alarm reset bit 10 measurement error al...

Page 12: ...ak alarm 16 sensor 2 clip break alarm 20 sensor 1 pressure measurement error 21 sensor 1 pressure measurement over range error 22 sensor 1 pressure measurement under range error 23 sensor 1 temperatur...

Page 13: ...onth enabled for cleaning 1 28 PA0009 1009 Cleaning start minute 1 1 0 59 59 PA0010 1010 Cleaning start hour 1 1 0 23 23 PA0013 1013 Maximum pressure delta in tenths of a KPa 1 1 100 150 5000 PA0017 1...

Page 14: ...14...

Reviews: