background image

10

11

12

Register 

name

Address 

(DEC)

Description

R

W

MIN

DEFAULT

MAX

Description of BIT

Data 

type

MON0000

0

Device model, represented with 

a 16-bit integer.

1

0

U16

MON0001

1

Device communication address 

or IDB, represented with an 

8-bit number.

1

0

U8

MON0002

2

Temperature measurement 1 in 

tenths of a degree, represented 

with a 16-bit integer.

1

0

U16

MON0003

3

Temperature measurement 2 in 

tenths of a degree, represented 

with a 16-bit integer.

1

0

U16

MON0004

4

Device model number, repre-

sented with a 16-bit integer.

1

0

U16

MON0005

5

Device serial number, repre-
sented with a 16-bit integer.

1

0

U16

MON0006

6

Measurement of delta pressure 

as (pressure 1 - pressure 2) in 

tenths of a KPa, represented 

with a 16-bit integer with sign.

1

0

I16

MON0009

9

Active alarm flags status repre-

sented with 16-bit integer, with 

the following meaning

1

0

bit 0 : no pressure on sensor 1 alarm
bit 1 : no pressure on sensor 2 alarm
bit 2 : leak detection alarm
bit 3 : seepage detection alarm
bit 4: inlet valve blocked alarm
bit 5: undefined
bit 6: drain valve blocked open alarm
bit 7: drain valve blocked closed alarm
bit 8: measurement error alarm on 
sensor 1, alarm with automatic alarm 
reset
bit 9: sensor 1 not correctly connected 
alarm, with automatic alarm reset
bit 10: measurement error alarm on 
sensor 2, alarm with automatic alarm 
reset
bit 11: sensor 2 not correctly connected 
alarm, with automatic alarm reset 
bit 12 : domestic water low pressure 
alarm
bit 13: air vent blocked alarm
bit 14: sensor 1 clip break alarm
bit 15: sensor 2 clip break alarm

U16

MON0011

11

status of the system faults 

flag represented with a 16-bit 

integer

1

0

bit 0: temperature 1 above maximum 
value set for drain
bit 1: temperature below minimum 
value, risk of frost
bit 2: pressure above maximum abso-
lute level
bit 3: temperature above maximum 
absolute level
bit 4: discharge air vent blocking 
condition
bit 5: filling not completed error
bit 6: pressure falling
bit 7: cleaning not successful error
bit 8: cleaning skipped error due to 
power loss

U16

MON0017

17

Day of the current week, repre-

sented with an 8-bit integer.

1

0

U8

MON0022

22

software version of the device, 

represented with an 8-bit 

integer.

1

0

U8

MON0023

23

software version of the device, 

represented with an 8-bit 

integer.

1

0

U8

MON0024

24

device firmware checksum, 

represented with a 16-bit 

integer

1

0

U16

Summary of Contents for DIRTMAGCLEAN 579 Series

Page 1: ...nel Display Operating principle Menu Forcing menu Parameters menu Historic data menu Communication Information Drainage temperature limitation Faults Alarm management 2 3 4 6 7 11 PROGRAMMING MANUAL C...

Page 2: ...ay The following information normally appears on the display Day of the week Probe S1 pressure Operating status Measured p Time Probe S1 temperature B battery alarm I input relay IN1 energized Operati...

Page 3: ...phase you can supply the necessary additives to the device 1 5 Automatic checks Use the UP or DOWN keys to select the submenu The regulator performs a periodic check on operation of the various strain...

Page 4: ...selected based on the plant characteristics values lower than 10kPa cannot be selected Delayed Dp When Dp exceeds a specified value the same value used to start the instantaneous cleaning cycle cleani...

Page 5: ...the alarm error code DATE and TIME show the exact moment when the alarm tripped 3 2 Faults Press OK to view the faults history The fault number is displayed with the associated code date and time of r...

Page 6: ...llowing the corrective action an alarms reset is required to allow the device to perform a loading cycle and assume correct operating status during this phase check that there are no anomalous operati...

Page 7: ...e network to have the actuator replaced isolate and empty the device disconnect the electric supply replace the motor and return the system to operation Perform the alarms reset fuses fault disconnect...

Page 8: ...his the plant must be de energised and the device must be emptied Once the new sensor has been installed proceed with the alarm reset E 23 sensor 1 temperature measurement error sensor internal fault...

Page 9: ...ARM 1 2 3 4 5 6 This connection can be made using a shielded twisted pair with minimum conductor size of 0 5 mm2 Maximum length of connections between one device and another is 2 95 m The cable must b...

Page 10: ...A ADDRESS Function 0x06 Write Single Register Used to write a single parameter 16 bit The frame has the following structure dev Addr Address of the device on the RS485 net 1 250 Func Function code 6 R...

Page 11: ...alve blocked closed alarm bit 8 measurement error alarm on sensor 1 alarm with automatic alarm reset bit 9 sensor 1 not correctly connected alarm with automatic alarm reset bit 10 measurement error al...

Page 12: ...ak alarm 16 sensor 2 clip break alarm 20 sensor 1 pressure measurement error 21 sensor 1 pressure measurement over range error 22 sensor 1 pressure measurement under range error 23 sensor 1 temperatur...

Page 13: ...onth enabled for cleaning 1 28 PA0009 1009 Cleaning start minute 1 1 0 59 59 PA0010 1010 Cleaning start hour 1 1 0 23 23 PA0013 1013 Maximum pressure delta in tenths of a KPa 1 1 100 150 5000 PA0017 1...

Page 14: ...14...

Reviews: