Function

The thermostatic mixing valve is used in solar thermal systems for
the production of domestic hot water.
It is designed to maintain the set temperature of the mixed water
supplied to the user when there are variations in the temperature
and pressure conditions of the incoming hot and cold water or in
the flow rate.

It is also fitted with an anti-scald safety function, which immediately
shuts off the hot water flow in case of a failure in the cold water
supply at the inlet.

This particular series of mixing valves can function continuously at
the high temperatures of the incoming hot water from the solar
storage tank.

Product range

2527 series Adjustable anti-scald thermostatic mixing valve for solar thermal systems.

Complete with strainers and check valves at the inlets

sizes 1/2” and 3/4”

Technical specifications

Materials

Body:

dezincification resistant alloy

EN 12165 CW602N, chrome plated

Obturator:

PSU

Springs:

stainless steel

Seal components:

EPDM

Control knob:

ABS

Performance

Adjustment range:

35–55°C

Accuracy:

±2°C

Max. working pressure (static):

10 bar

Max. working pressure (dynamic):

5 bar

Max. inlet temperature:

100°C

Max. inlet pressure ratio (H/C or C/H):

2:1

Minimum temperature difference between the inlet hot water 
and the outlet mixed water to ensure anti-scald performance: 10°C
Min. flow rate for stable operation: 

4 l/min

Performance to standards:

NF 079 doc. 8, EN 15092 

EN 1111, EN 1287

Connections:

1/2” and 3/4” M with union

Dimensions

CALEFFI

R

E

G

I STERE

D

BS EN ISO 9001:2000

Cert. n

°

 FM 21654

UNI EN ISO 9001:2000

Cert. n

°

 0003

A

1/2”
3/4”

E

81,5

82

D

126,5

127

F

45
45

C

125
134

B

62,5

67

Code

2527

14

2527

13

Weight (kg)

0,58
0,81

F

E

D

B

B

C

A

A

A

Reviews: