Modbuskonfigurering.
7
Modbus configuration.
DIPSWITCH
* Måste väljas före driftsättning.
* Must be configurated before power up.
TERMINERING
MODBUSREGISTER
Discrete Inputs
Address
Comment
Min
Max
1x0001
Detector mounted in base
0
1
1x0002
Service alarm
0
1
1x0003
Smoke alarm
0
1
Holding Registers
Address
Comment
4x0001
Reset smoke alarm
234 = reset alarm
1 = Set to normal
Jumper 1 ON
RS485+ 4.7 kOhm Pull-up
Jumper 2 ON
120 Ohm Termination
Jumper 3 ON
RS485- 4.7 kOhm Pull-down
Pos.
ON
OFF
1
Address 0=1 (binary)
Address 0=0 (binary)
2
Address 1=1 (binary)
Address 1=0 (binary)
3
Address 2=1 (binary)
Address 2=0 (binary)
4
Address 3=1 (binary)
Address 3=0 (binary)
5
Address 4=1 (binary)
Address 4=0 (binary)
6
Address 5=1 (binary)
Address 5=0 (binary)
7
Address 6=1 (binary)
Address 6=0 (binary)
8
Address 7=1 (binary)
Address 7=0 (binary)
9
1 startbit, 1 stop bit, Even parity*
1 startbit, 2 stop bits, No parity*
10
38400 baud rate*
9600 baud rate*