your selection with Enter.

6. Use the arrow buttons to step, and confirm Exit-

Menu to terminate and save setting.

9.  SETTING OF PREFERED VALUES/SET POINT

To change set points press ▲ or ▼ to achieve the 

desired value. The set point value will flash during 
setting. Confirm and terminate with Enter (

). In 

cases where the selected application contains two 
set point values the next value will now start to flash. 

Change with ▲ or ▼ to the desired value and confirm 

with Enter (

). Done!

Enter

<

<

°

C

1







Set point values and relays:

1-stage applications: 

- The reference value to the left controls the function 
for relay 1.

2-stage applications:

- The reference value to the left controls the function 
for relay 1. 

- The reference value to the right controls the func-
tion for relay 2.

Example:

Set point value for relay 1 is displayed in the upper 
left-hand corner: The 'less-than' symbol (<) indicates 
that the relay is calling for heat when the temperature 
is lower than the set point value = heating function.

Set point value for relay 2 is displayed in the upper 
right-hand corner: The 'greater than' symbol (>) indi-
cates that the relay is calling for cooling when the 
temperature is higher than the set point value = coo-
ling function.

Selectable applications

Appl.

Function

Factory settings

Reference 
value °C 
stage 1

Reference 
value °C 
stage 2

Hysteresis 
°C stage 1

Hysteresis 
°C stage 2

Time setting in 
minutes (adjustable)

1

1-stage heating thermostat

23

-

0,6

-

2

1-stage cooling thermostat

25

-

1

-

3

2-stage heating thermostat

23

21

0,6

0,6

4

2-stage cooling thermostat

25

27

1

1

5

2-stage heating and cooling thermostat

22

24

0,6

1

6

1-stage cooling thermostat with low temperature 
alarm *1

5

1

1

0

0 (0-120) *3

7

1-stage heating thermostat with overheating alarm *1

50

85

0,6

0

0 (0-120) *3

8

2-stage overheating alarm *1

40

60

0

0

0 (0-120) *3

9

High and low temperature alarm *1

8

3

0

0

0 (0-120) *3

10

Gutter thermostat *2, relay 2 = fault alarm

-5

5

0,6

0,6

0 (0-120) *4

11

Gutter thermostat *2 with whole numbers, relay 2 = 
fault alarm

-5

5

0,6

0,6

0 (0-120) *4

*1) The alarm relay is activated in normal oper-
ational mode and is deactivated in the event of 
an alarm or power loss. In the event of an alarm 
"ALARM" is displayed under the respective 
alarm reference value.

*2) Double thermostat where relay 1 activate 
heating when the outside temperature is 
between set point 1 and 2 (the temperature at 
which snow on a roof can melt and form icicles).

*3) Delayed alarm time, e.g. to allow for defrost-
ing.

*4) After-running time: To ensure de-icing.

In the event of alarm (applications 6-9) the 
relay(s) are locked in the alarm condition until the 
Reset button has been depressed. If the alarm 
condition reverted to "normal temperature" when 
the Reset button was depressed, the relay is 
reset and the central button reverts to the Menu 
function.
If the alarm condition persists, when press-
ing the Reset button, the relay will not be reset. 
However, the central button reverts to Menu 
function for 5 seconds in order to allow settings 
in the menu system, or in order to change appli-
cation.
The set point values and alarm reference values 
can always be adjusted even during an alarm 
condition. See section 9.

CMT has a monitor for the temperature sensor 
and disconnects from heating or cooling in the 
event of short-circuit or interruption in the sen-
sor circuit. However this is not valid for the gutter 
thermostat function in application 10.

8.  SELECTION OF TEMPERATURE 

SENSOR

CMT can be connected to several different types 
of temperature sensor: Pt100, Pt1000, Ni1000 
and the ETF series for Calectro's NTC and PTC 
sensors. Pt1000 is the factory set sensor type.

2. Press the Menu button (

) to access the 

menu system

3. The actual type of temperature sensor will 

be displayed.

4. Press Menu-Enter to change the type of 

temperature sensor

5. The actual sensor type now starts to flash 

and it is now possible to select another sen-
sor type using the arrow buttons. Confirm 

<

1 2

>





10.  SETTING OF HYSTERESIS

CMT has an adjustable hysteresis (switching 
differential) which is centred over the set point 
value.  The factory setting for the heating ther-
mostat is 0.6°C and for the cooling thermostat 
1.0°C. 

Example: A heating thermostat with set point 
value of 22°C and hysteresis 0.6°C. The relay 
activates the heater at lower than 21.7°C and 
reverts at greater than 22.3°C.

Temperature

Relay

0

21,7

0,3°C

0,3°C

22

22,3

1

Set point

No hysteresis is used for alarm functions.

1.  Press the Menu button (

) to access the 

menu system

2. Step using the arrow buttons until "Hyst" is 

shown on the display.

3. Press Menu-Enter to change hysteresis.

4. The actual hysteresis now starts to flash 

and it is now possible to adjust the hyster-
esis using the arrow buttons. Confirm your 
selection with Enter (

).

5. Use the arrow buttons to step, and confirm 

Exit-Menu to terminate and save setting.