III.3.

 

III.3 2 speeds motors 

 

2 speeds 

 1 voltage (Dhalander wiring) 400 V 

 2/4 or 4/8 poles motors 

Low speed 

High speed 

 

 

 

III.4.

 

III.4 2 speeds motors (separate windings) 

 

2 speeds 

 1 voltage (separate windings) 400 V 

 4/6 poles motors 

Low speed 

High speed 

 

 

 

Once wiring is done, check if the impeller is turning in the right direction. If not, reverse two phases and check again. 
Please note that a fan running in the wrong direction 

doesn’t

 drive air in the opposite direction, but only provide lower airflow than expected.  

 

Summary of Contents for PYROSTAR F400-120

Page 1: ...PYROSTAR SMOKE FAN F400 120 MS MTG 001 Ind E 01 10 2019 Page 1 8 INSTALLATION AND COMMISSIONING MANUAL...

Page 2: ...I 1 Handling 3 II 2 Space required for maintenance 4 II 3 II 3 Installation 4 III ELECTRICAL WIRING 4 III 1 Wiring 4 III 2 1 speed motors 4 III 3 III 3 2 speeds motors 5 III 4 III 4 2 speeds motors se...

Page 3: ...handled using a fork lift truck ensure this supports the load bearing structure and does not touch the panels enclosing the unit If the device is moved using a crane use four cables of identical lengt...

Page 4: ...outdoor or when installed indoor separated from other volumes by a 1 hour fire resistant wall The door of the technical room should be hour fire resistant Ventilation of this technical room should com...

Page 5: ...4 III 4 2 speeds motors separate windings 2 speeds 1 voltage separate windings 400 V 4 6 poles motors Low speed High speed Once wiring is done check if the impeller is turning in the right direction I...

Page 6: ...eck pulleys alignment both motor and impeller pulleys along with belt tension IV 2 IV 2 Belt tension Please refer to the following table for belt s tension I pulleys axle spacing F belt deflection P f...

Page 7: ...rflow After settings make sure both locking screws are secured and the the pulleys alignment is fine V Troubleshooting Problem Main reasons How to solve Fan not running Main power off Thermal motor pr...

Page 8: ...PYROSTAR SMOKE FAN F400 120 MS MTG 001 Ind E 01 10 2019 Page 8 8 VI NOTES Date Observations...

Reviews: